41
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
2240
O
Switching differential boiler
1
0
20
°C
2241
O
Burner running time min
2
0
20
min
2250
O
Pump overrun time
5
0
20
min
2260
O
Prot boil startup consumers
Off ¦ On
Off
-
-
-
2261
O
Prot boil startup boil pump
Off ¦ On
Off
-
-
-
2262
O
Optimum start control
Off ¦ On
Off
-
-
-
2270
F
Return setpoint min
8
8
95
°C
2271
O
Return setpoint min OEM
30
8
95
°C
2272
O
Return influence consumers
Off ¦ On
On
-
-
-
2282
O
Actuator running time
120
30
873
s
2283
O
Mixing valve Xp
32
1
100
°C
2284
O
Mixing valve Tn
120
10
873
s
2285
O
Mixing valve Tv
10
0
60
s
2290
O
Switching diff bypass pump
6
0
20
°C
2291
O
Control bypass pump
Parallel burner operation ¦ Return temp
Return temperature
-
-
-
2300
O
Frost prot plant boiler pump
Off ¦ On
Off
-
-
-
2310
O
Limit thermostat function
Off ¦ On
On
-
-
-
2315 (***)
O
Temp differential min
- - -
- - -/ 0
80
°C
2316
O
Temp differential max
-
0
80
°C
2317(**)
O
Temp differential nominal
10
0
80
°C
2320(**)
O
Pump modulation
None ¦ Demand ¦ Boiler setpoint ¦ Temp differential nominal ¦
Burner output
Burner output
-
-
-
2322
F
Pump speed min
40
0
100
%
2323
F
Pump speed max
100
0
100
%
2324 (***)
O
Speed Xp
32
1
100
°C
2325 (***)
O
Speed Tn
120
10
873
s
2326(***)
O
Speed Tv
10
0
60
s
2330
F
Output nominal
50
0
1000
kW
2331
F
Output basic stage
30
0
1000
kW
2340(***)
F
Auto source seq 2x1 casc
500
- - -/ 10
990
h
Cascade
3510
O
Lead strategy
Late on, early off ¦ Late on, late off ¦ Early on, late off
Late on, late off
-
-
-
3511
O
Output band min
40
0
100
%
3512
O
Output band max
90
0
100
%
3530
O
Release integral source seq
50
0
500
°C min
3531
O
Reset integral source seq
20
0
500
°C min
3532
F
Restart lock
300
0
1800
s
3533
F
Switch on delay
5
0
120
min
3534
O
Forced time basic stage
0
0
1200
s
3540
F
Auto source seq ch’over
500
- - - / 10
990
h
3541
F
Auto source seq exclusion
None ¦ First ¦ Last ¦ First and last
None
-
-
-
3544
F
Leading source
Heat source 1 ¦ Heat source 2 ¦ … ¦ Heat source 16
Heat source 1
-
-
-
3550
O
Prot startup cascade pump
Off ¦ On
Off
-
-
-
3560
F
Return setpoint min
8
8
95
°C
3561
O
Return setpoint min OEM
8
8
95
°C
3562
O
Return influence consumers
Off ¦ On
On
-
-
-
3570
F
Actuator running time
120
30
873
s
3571
O
Mixing valve Xp
24
1
100
°C
3572
O
Mixing valve Tn
90
10
873
s