39
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
1641
F
Legionella funct periodically
3
1
7
Days
1642
F
Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦ Saturday ¦
Sunday
Monday
-
-
-
1644
F
Legionella funct time
- - -
- - - /
00:00
23:50
hh:mm
1645
F
Legionella funct setpoint
65
55
95
°C
1646
F
Legionella funct duration
30
- - - / 10
360
min
1647
F
Legionella funct circ pump
Off ¦ On
On
-
-
-
1648(**)
F
Legio funct circ temp diff
- - -
- - - / 0
20
°C
1660
F
Circulating pump release
Time program 3/HCP ¦ DHW release ¦ Time program 4/DHW¦ Time
program 5
DHW release
-
-
-
1661
F
Circulating pump cycling
Off ¦ On
On
-
-
-
1663
F
Circulation setpoint
45
8
80
°C
1680(**)
F
Optg mode changeover
None ¦ Off ¦ On
Off
-
-
-
Pumps H
2008(***)
O
H1 DHW charging priority
No ¦ Yes
Yes
-
-
-
2010(***)
F
H1 Excess heat draw
Off ¦ On
On
-
-
-
2012(***)
F
H1 with buffer storage tank
No ¦ Yes
Yes
-
-
-
2014(***)
F
H1 prim contr/system pump No ¦ Yes
Yes
-
-
-
2033(***)
O
H2 DHW charging priority
No ¦ Yes
Yes
-
-
-
2035(***)
F
H2 Excess heat draw
Off ¦ On
On
-
-
-
2037(***)
F
H2 with buffer storage tank
No ¦ Yes
Yes
-
-
-
2039(***)
F
H2 prim contr/system pump
No ¦ Yes
Yes
-
-
-
2046(***)
F
H3 Excess heat draw
Off ¦ On
On
-
-
-
2048(***)
F
H3 with buffer
No ¦ Yes
Yes
-
-
-
2050(***)
F
H2 prim contr/system pump
No ¦ Yes
Yes
-
-
-
Consumer circuit 1
1859(**)
I
Flow temp setp cons request
70
8
120
°C
1860(**)
F
Frost prot plant CC pump
Off ¦ On
On
-
-
-
1874(**)
O
DHW charging priority
No ¦ Yes
Yes
-
-
-
1875(**)
F
Excess heat draw
Off ¦ On
On
-
-
-
1878(**)
F
With buffer
No ¦ Yes
Yes
-
-
-
1880(**)
F
With prim contr/system pump
No ¦ Yes
Yes
-
-
-
Consumer circuit 2
1909(**)
I
Flow temp setp cons request
70
8
120
°C
1910(**)
F
Frost prot plant CC pump
Off ¦ On
On
-
-
-
1924(**)
O
DHW charging priority
No ¦ Yes
Yes
-
-
-
1925(**)
F
Excess heat draw
Off ¦ On
On
-
-
-
1928(**)
F
With buffer
No ¦ Yes
Yes
-
-
-
1930(**)
F
With prim contr/system pump
No ¦ Yes
Yes
-
-
-