37
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
1050
F
Room influence
20
- - - / 1
100
%
1060
F
Room temp limitation
1
- - - /
0.5
4
°C
1070
F
Boost heating
3
- - - / 0
20
°C
1080
F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
Down to reduced set
point
-
-
-
1090
F
Optimum start control max
0
0
360
min
1091
F
Optimum stop control max
0
0
360
min
1094(**)
F
Heat up gradient
60
0
600
Min/K
1100
F
Reduced setp increase start
- - -
- - - /
-30
10
°C
1101
F
Reduced setp increase end
-15
-30
OL 1100
°C
1110(**)
F
Frost prot plant HC pump
Off ¦ On
On
-
-
-
1120
F
Overtemp prot pump circuit
Off ¦ On
On
-
-
-
1130
F
Mixing valve boost
5
0
50
°C
1132
F
Actuator type
2-position ¦ 3-position
3-position
-
-
-
1133
F
Switching differential 2-pos
2
0
20
°C
1134
F
Actuator running time
120
30
873
s
1135
O
Mixing valve Xp
24
1
100
°C
1136
O
Mixing valve Tn
90
10
873
s
1150
F
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing heat-
ing ¦ Curing/functional heating ¦ Manually
Off
-
-
-
1151
F
Floor curing setp manually
25
0
95
°C
1156(**)
I
Floor curing day current
0
0
32
-
1157(**)
I
Floor curing days completed
0
0
32
-
1161
F
Excess heat draw
Off ¦ Heating mode ¦ Always
Always
-
-
-
1170
F
With buffer
No ¦ Yes
Yes
-
-
-
1172
F
With prim contr/system pump
No ¦ Yes
Yes
-
-
-
1180(**)
F
Pump speed reduction
Operating level ¦ Characteristic
Characteristic
-
-
-
1182
F
Pump speed min
40
0
OL 1183
%
1183
F
Pump speed max
100
OL 1182
100
%
1188(**)
O
Curve readj at 50% speed
33
0
100
%
1190(**)
O
Flow setp readj speed ctrl
No ¦ Yes
Yes
-
-
-
1200
F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection mode
-
-
-
Heating circuit 3
1300
E
Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatically
-
-
-
1310
E
Comfort setpoint
20,0
OL 1312
OL 1316
°C
1312
E
Reduced setpoint
16
OL 1314
OL 1310
°C
1314
E
Frost protection setpoint
10,0
4
OL 1312
°C
1316
F
Comfort setpoint max
35,0
OL 1310
35
°C
1320
E
Heating curve slope
1,50
0,10
4,00
-
1321
F
Heating curve displacement
0,0
-4,5
4,5
°C
1326
F
Heating curve adaption
Off ¦ On
Off
-
-
-
1330
E
Summer/winter heating limit
18
- - - / 8
30
°C
1332
F
24-hour heating limit
-3
- - - /
-10
10
°C
1333(**)
O
Ext’n 24-hour heating limit
No ¦ Yes
Yes
-
-
-
1340
F
Flow temp setpoint min
8
8
OL 1341
°C
1341
F
Flow temp setpoint max
80
OL 1340
95
°C