38
RIELLOTECH CLIMA TOP - CLIMA COMFORT
RIELLOTECH CLIMA TOP - CLIMA COMFORT
Operat-
ing line
User
level Function
Default value
Min
Max
Unit
1342(**)
F
Flow temp setpoint room stat
65
OL 1340
OL 1341
°C
1344(**)
O
Swi-on ratio room stat
- - -
- - - / 1
99
%
1350
F
Room influence
20
- - - / 1
100
%
1360
F
Room temp limitation
1
- - - /
0.5
4
°C
1370
F
Boost heating
3
- - - / 0
20
°C
1380
F
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot setpoint
Down to reduced set
point
-
-
-
1390
F
Optimum start control max
0
0
360
min
1391
F
Optimum stop control max
0
0
360
min
1394(**)
F
Heat up gradient
60
0
600
Min/K
1400
F
Reduced setp increase start
- - -
- - - /
-30
10
°C
1401
F
Reduced setp increase end
-15
-30
OL 1400
°C
1410(**)
F
Frost prot plant HC pump
Off ¦ On
On
-
-
-
1420
F
Overtemp prot pump circuit
Off ¦ On
On
-
-
-
1430(**)
F
Mixing valve boost
5
0
50
°C
1432(**)
F
Actuator type
2-position ¦ 3-position
3-position
-
-
-
1433(**)
F
Switching differential 2-pos
2
0
20
°C
1434(**)
F
Actuator running time
120
30
873
s
1435(**)
O
Mixing valve Xp
24
1
100
°C
1436(**)
O
Mixing valve Tn
90
10
873
s
1450
I
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing heat-
ing ¦ Curing/functional heating ¦ Manually
Off
-
-
-
1451
I
Floor curing setp manually
25
0
95
°C
1455(***)
F
Floor curing setp current
0
0
95
°C
1456
I
Floor curing day current
0
0
32
-
1457 (**)
I
Floor curing days completed
0
0
32
-
1461
F
Excess heat draw
Off ¦ Heating mode ¦ Always
Always
-
-
-
1470
F
With buffer
No ¦ Yes
Yes
-
-
-
1472
F
With prim contr/system pump
No ¦ Yes
Yes
-
-
-
1480(**)
F
Pump speed reduction
Operating level ¦ Characteristic
Characteristic
-
-
-
1482
F
Pump speed min
40
0
OL 1483
%
1483
F
Pump speed max
100
OL 1482
100
%
1488(**)
O
Curve readj at 50% speed
33
0
100
%
1490(**)
O
Flow setp readj speed ctrl
No ¦ Yes
Yes
-
-
-
1500
F
Optg mode changeover
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic
Protection mode
-
-
-
Domestic hot water DHW
1600
E
DHW operating mode
Off ¦ On
On
-
-
-
1601(**)
O
Optg mode selection Eco
None ¦ Instantaneous water heater ¦ DHW storage tank ¦ Inst wa-
ter st tank
None
-
-
-
1610
E
Nominal setpoint
55
OL 1612
OL 1614
OEM
°C
1612
F
Reduced setpoint
40
8
OL 1610
°C
1614
O
Nominal setpoint max
65
8
80
°C
1620
I
Release
24h/day ¦ Time programs HCs ¦ Time program 4/DHW
Time programs HCs
-
-
-
1630
I
Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
MC shifting, PC abso-
lute
-
-
-
1640
F
Legionella function
Off ¦ Periodically ¦ Fixed weekday
Fixed weekday
-
-
-