FAMILY CX

INSTALLATION MANUAL

DESCRIPTION

The 

Family

  boilers  have  a  new ACC  combustion  control  system  (active 

combustion control).
This new control system, developed by 

Riello

, in all circumstances provides 

functionality, effi  ciency and low emissions. 

The ACC system uses an ionisation sensor immersed in the burner fl ame, 

whose information allows the control board to operate the gas valve that 

regulates the fuel.

This sophisticated control system provides for the auto adjustment of the 

combustion, thereby eliminating the need for an initial calibration 

The  ACC  system  can  adapt  the  boiler  to  operate  with  diff erent  gas 

compositions, diff erent pipe lengths and various altitudes (within the design 

limits).

The ACC system can also perform an auto-diagnostic operation that locks 
out the burner before the permitted upper emission limit is exceeded.

Family  

is a type C condensing wall-hung boiler to be used for heating and 

the  production  of  domestic  hot  water:  Depending  on  the  fume  discharge 
accessory  used,  it  is  classifi ed  in  categories  B23P;  B53P;  C13,C13x; 
C33,C33x; C43,C43x; C53,C53x; C83, C83x; C93, C93x.
In  confi guration  B23P  (when  installed  indoors),  the  appliance  cannot 
be  installed  in  bedrooms,  bathrooms,  showers  or  where  there  are  open 
fi replaces without a proper air fl ow. The room where the boiler is installed 
must have proper ventilation. Detailed requirements for the installation of 
the fl ue, the gas piping and for ventilating the room, can be found in UNI 
7129-7131. 
In confi guration C, the appliance can be installed in any type of room and 
there are no limitations due to ventilation conditions or room volume.

3  INSTALLATION

3.1 

Cleaning the system and characteristics of the water

In the case of a new installation or replacement of the boiler, it is necessary 
to clean the heating system.
To  ensure  the  device  works  well,  top  up  the  additives  and/or  chemical 
treatments  (e.g.  anti-freeze  liquids,  fi lming  agents,  etc.)  and  check  the 
parameters in the table are within the values indicated.

PARAMETERS

UM

HEATING CIRCUIT 

WATER

FILLING WATER

pH value

7–8

-

Hardness

°F

-

< 15

Appearance

-

clear

Fe

mg/kg

0.5

-

Cu

mg/kg

0.1

-

3.2 

Receiving the product

The 

Family 

boiler  is  shipped  in  a  single  pack,  protected  by  cardboard 

packaging.

The boiler is supplied as standard with the following material:

 

-  Instruction booklet for the user

 

- Instructions  booklet  for  the  installer  and  for  the  technical  assistance 

service

 

- Bar code labels

 

- Pre-assembly template

 

- Package with plumbing fi ttings

 

- Bypass valve

 

- Flat gasket

 

- SRD device 

 

- Condensate drain pipe

 

- Flexible hose safety valve

 

- Electric connections box

 

b

The instruction booklets are an integral part of the boiler and there 

it is recommended to read them carefully and keep them in a safe 
place.

3.3 

Dimensions and weights (fi g. 5)

FAMILY

25 KIS

30 KIS

35 KIS

L

470

470

470

mm

P

275

350

350

mm

H

740

740

740

mm

H1

822

822

822

mm

Net Weight

35

40

40

kg

3.4 

Handling (Fig. 6)

After unpacking, handling of the boiler is done manually using the support 
frame.

3.5 

Installation room

The 

Family 

boiler can be installed in various types of room, as long as the 

discharge  of  the  combustion  product  and  the  combustion  air  suction  are 

outside the room itself. 

In  this  case  the  room  does  not  need  any  ventilation  opening  since  the 

Family

 boilers have a combustion circuit that is "airtight" with respect to the 

installation environment.

 

b

Consider the clearances necessary to access safety and adjustment 

devices and to perform maintenance operations.

 

b

Check that the electric protection level of the appliance is adapted to 

the installation room characteristics.

 

b

If the boilers are supplied with fuel gas of a specifi c weight greater 

than that of the air, the electric parts will have to be positioned more 
than 500mm above ground level.

3.6 

Installation on appliances that are old or that 

need to be updated

When  the 

Family 

boiler  is  installed  in  old  systems  or  systems  being 

updated, check that:

 

- The fl ue is suitable for the temperature of the combustion products with 

condensation, calculated and built according to Standard, is as straight 
as possible, airtight, insulated and has no blockages or narrow sections. 
It  is  equipped  with  appropriate  condensate  collection  and  discharge 
systems

 

- The electrical system is installed in compliance with the specifi c standards 

and by qualifi ed personnel

 

- The  fuel  supply  line  and  eventual  tank  (LPG)  are  made  according  to 

specifi c Standards

 

- The expansion tank ensures the total absorption of the dilatation of the 

fl uid contained in the system

 

- The fl ow rate and head of the circulator are suitable to the characteristics 

of the system

 

- The  system  is  washed,  cleansed  of  any  mud,  build-up,  vented  and 

sealed.  It  is  recommended  that  a  magnetic  fi lter  be  installed  on  the 
system's return line

 

- The boiler condensate drain system (siphon) is connected and routed to 

the collection of "white" water

3.7 

Installation regulations

The installation must be carried out by qualifi ed personnel, in compliance 

with the following reference standards:

 

- UNI 7129-7131

 

- CEI 64-8.

Always  comply  with  local  standards  of  the  Fire  Department,  the  Gas 
Company and with possible municipal dispositions.

POSITION

Family 

 is a wall-hung boiler for heating and for the production of hot water, 

that comes in two categories, depending on the type of installation:

 

-  B23P-B53P type boiler - forced open installation, with fl ue gas discharge 

pipe and pick-up of combustion air from the installation area. If the boiler 
is not installed outdoors, air intake in the installation area is compulsory.

 

-  C13,  C13x  type  boiler;  C33,  C33x;  C43,  C43x;  C53,C53x;  C83,  C83x, 

C93, C93x: appliance with airtight chamber, with fl ue gas discharge pipe 
and  pick-up  of  combustion  air  from  outside.  It  does  not  require  an  air 
intake point in the installation area. This type MUST be installed using 
concentric  pipes,  or  other  types  of  discharge  designed  for  condensing 
boilers with an airtight chamber.

Family 

can be installed outdoors, in a partially protected place (i.e. a place 

where the boiler is not exposed to direct contact or infi ltration of rain, snow 

or hail. The boiler can operate in a temperature range from -5°C to +60°C.

Summary of Contents for Family 25 KIS

Page 1: ...Family KIS EN INSTALLER AND USER MANUAL RO MANUAL DE INSTALARE SI UTILIZARE...

Page 2: ...references 0051 Manual de instalare utilizare 47 91 Elementele func ionale ale centralei 92 Scheme electrice 93 Circuit hidraulic 94 Cap rezidual pomp de circula ie 95 Centrala termic Family respect...

Page 3: ...hat b In the event of water leaks the water supply must be shut o and the Technical Assistance Centre contacted immediately b Periodically check that the operating pressure of the hydraulic system is...

Page 4: ...y using the support frame 3 5 Installation room The Family boiler can be installed in various types of room as long as the discharge of the combustion product and the combustion air suction are outsid...

Page 5: ...oning the wall mounted boiler and hydraulic connections Fig 10 The boiler comes as standard with a boiler support plate The position and dimension of hydraulic ttings are shown in the detail drawing F...

Page 6: ...only original pipes be used except C6 and that the connection is made correctly as shown in the instructions provided with the ue gases accessories A single ue can be connected to several appliances p...

Page 7: ...P1 The boilers are factory set to 25 KIS 6 200 r p m in heating mode and 7 600 in domestic hot water mode and the maximum attainable length is 5m for the 50 pipe 18 m for the 60 pipe and 98 m for the...

Page 8: ...lly closing the de aeration tap A Note even if the boiler is tted with a semi automatic lling device the rst lling operation must be carried out by turning the ller tap B with the boiler OFF Note each...

Page 9: ...disabled Press button A for more than 2 seconds until the LEDs start blinking Pressing button A brie y within a period of no more than 10 seconds the user interface will display the next settings The...

Page 10: ...le On the left and right sides are displayed the icons indicating the status of the system their meaning is the following The display of the REC10 control panel is equipped with the new Color Bar that...

Page 11: ...DIRECT ZONE DIRECT ZONE MIXING ZONE INSTALLER Only zones with ACTUATION BE16 ZONE TYPE HIGH TEMP HIGH TEMP LOW TEMP INSTALLER MIN CH SET 40 C AT 20 C BT 20 C MAX CH SET INSTALLER MAX CH SET 80 5 C AT...

Page 12: ...F HIGH TEMP 5 C 2 C 10 C SERVICE HYST ON LOW TEMP 3 C 2 C 10 C SERVICE HYST OFF LOW TEMP 3 C 2 C 10 C SERVICE SP INCR HIGH TEMP 5 C 0 C 10 C SERVICE SP INCR LOW TEMP 0 C 0 C 6 C SERVICE DECR COOLING S...

Page 13: ...C INSTALLER If request type AMBIENT PROBE or REC10 COOLING 18 C 4 C 20 C INSTALLER BUILDING TYPE 5 min 5 min 20 min INSTALLER Only if EXTERNAL PROBE connected OUTDOOR REACTIVITY 20 0 255 INSTALLER Onl...

Page 14: ...ELTA T OFF PUMP 4 C 4 C DELTA T ON PUMP INSTALLER INTEGRATION DELAY 0 min 0 min 199 min INSTALLER COLLECTOR T MIN 30 C 0 C INSTALLER COLLECTOR T MAX 110 C COLLECTOR T PROT 180 C INSTALLER COLLECTOR T...

Page 15: ...AITING 2 min 1 min 60 min SERVICE INTEGRATION OFFSET 5 C 0 C 10 C SERVICE WINTER SUMMER DELAY 0h 0h 24h SERVICE WARNING VALIDATION 60 sec 1 sec 300 sec SERVICE ENABLE CIRC AUTO MODE ENABLE CIRC ON MOD...

Page 16: ...ue gases and the air suction pipes are working correctly that conditions for regular maintenance are guaranteed if the boiler is placed inside or between items of furniture the seal of the fuel adduct...

Page 17: ...NG TIMING OFF regarding the delay time introduced for re igniting the burner in the face of an off due to the heating temperature being reached The factory setting for this parameter is 3 minutes and...

Page 18: ...he UP and DOWN keys and confirm the selection PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION TECHNICAL INSTALLER SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLATION INSTAL...

Page 19: ...the THERMOREGULATION function The temperature measured by the outdoor temperature sensor is displayed on the initial page in the top right alternating with the display of the time When thermoregulati...

Page 20: ...enever a programmable timer is connected to the ROOM THERMOSTAT input from the TECHNICAL THERMOREGULATION CLIMATIC CURVES MAIN the NIGHT COMPENSATION function can be enabled In this case when the CONT...

Page 21: ...ing the heating water temperature without an outdoor temperature sensor connected When there is no outdoor temperature sensor the boiler operates at a fixed point the HEATING setpoint in this case can...

Page 22: ...e signalling faults will ash on the REC10 To identify the fault codes and to reset the appliance see the section Signals and faults E010 PRESS OK TO RESET FLAME LOCKOUT 5 9 Reset function In the event...

Page 23: ...the combustion OFF HOT WATER ONLY HEATING AND HOT WATER BOILER 5 12 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This oper...

Page 24: ...hat shown in the technical data table DO NOT CARRY OUT ANY ADJUSTMENTS OF THE GAS VALVE ask for help from the Technical Assistance Centre b The gas valve DOES NOT need adjusting and any tampering with...

Page 25: ...ng the BACK key it is possible to return to the main screen where the presence of the fault is indicated by the flashing icon 1 3 bar 42 C MENU STATE SET INFO PLANT HOT WATER TEMPERATURE FRI 18 05 201...

Page 26: ...rmally but does not provide any stability of the domestic hot water temperature that in any event is supplied at a temperature of around 50 C The intervention of the Technical Assistance Service is re...

Page 27: ...ost transitional Red BUS 485 communication lost transitional List of combustion faults ERROR CODE COLOUR DISPLAYED ERROR MESSAGE DESCRIPTION OF TYPE OF ALARM E021 Red ion alarm These are temporary ala...

Page 28: ...ivated if the temperature measured by the flow sensor drops below 5 C A heat request is generated in this phase with the ignition of the burner at minimum output which is maintained until the outlet w...

Page 29: ...lect the desired options with the UP and DOWN keys confirming the selection PRESS ANY KEY TO CONTINUE REC10R R02 06 Welcome at home LANGUAGE selection ENGLISH ENGLISH ROMANESC ENGLISH ITALIANO setting...

Page 30: ...eplacing the REC10 MASTER at the subsequent restart it displays an initial screen with the firmware revision Pressing ENTER starts a guided procedure for configuring the system see the section Configu...

Page 31: ...duration of the boiler It allows for the reduction of consumption polluting emissions and keeping the product reliable over time Before starting maintenance operations Close the fuel and water taps of...

Page 32: ...lectrodes At this point proceed with the burner cleaning operations Clean the burner with a soft bristled brush being careful not to damage the insulating panel and the electrodes DO NOT USE METAL BRU...

Page 33: ...conveyor and take it out together with the gasket E Change the burner Put back the burner working in the opposite direction to what has been described remembering to put in the relative gasket Removin...

Page 34: ...ain zone is in MANUAL mode the management of the heating requests does not follow what has been set with the programming timing but it is always active OFF This icon indicates that the system main zon...

Page 35: ...ction can be used to set the BOILER and MAIN ZONE operating modes To do this it is necessary to highlight the desired entry using the up and down keys and then pressing ok to con rm the selection Pres...

Page 36: ...is then asked to confirm the setpoint setting select CONFIRM or CANCEL using the up and down keys and confirm the selection pressing ok Once the selection is confirmed the display returns to the SET...

Page 37: ...p and down keys to change the desired values Once the sequence has nished by pressing ok the settings will be saved and the display will return to the initial screen By pressing back at any time the s...

Page 38: ...to increase or decrease by 30 minutes the end time and press ok to con rm the selection 07 30 15 00 08 30 11 30 13 30 18 30 14 00 22 30 START MAIN THURSDAY USE THE ARROWS TO MODIFY ENTER ADD END TIME...

Page 39: ...rm that the operation has been completed successfully the display will show the table with the selected time frame ashing just before deleting it from the table 07 30 08 30 11 30 13 30 18 30 22 30 MAI...

Page 40: ...ease the alarm before the end of the post purging unless the boiler s power supply is switched o E094 incomplete combustion ON E095 incomplete combustion ON E058 mains voltage fault ON These are tempo...

Page 41: ...ps frequently contact the Technical Assistance Centre A For fault E091 The boiler has an auto diagnostic system which based on the total number of hours in certain operating conditions can signal the...

Page 42: ...0 97 4 97 1 97 3 97 4 97 4 97 4 Combustion e ciency 97 8 97 6 97 7 Useful e ciency Pn max Pn min 50 30 106 2 105 8 106 0 104 7 106 9 104 7 Useful e ciency 30 Pn max 30 return 108 4 108 1 108 2 E cienc...

Page 43: ...head of boiler without pipes Pa 180 170 195 Concentric ue gas outlet pipes Diameter mm 60 100 60 100 60 100 Maximum length m 10 6 6 Losses for a 45 90 bend m 1 3 1 6 1 3 1 6 1 3 1 6 Hole in wall diame...

Page 44: ...DHW minimum gas capacity Sm h 0 52 kg h 0 54 Number of fan rotations with slow ignition rpm 5 500 5 500 Maximum number of heating fan rotations rpm 5 800 5 600 Maximum number of DHW fan rotations rpm...

Page 45: ...ing boilers 30 C for low temperature boilers 37 C for other heating appliances 50 C of return temperature Family Cx 25 KIS Seasonal ambient heating energy e ciency class A Water heating energy e cienc...

Page 46: ...1 97 5 Auxiliaryelectricconsumption Otherparameters Withfullload elmax 28 0 W Heatlossesin andbymode P by 32 0 W Withpartialload elmin 14 0 W Energyconsumptionofthepilotlight Pign W In andby PSB 3 0 W...

Page 47: ...m toarele aspecte b n cazul scurgerilor de ap alimentarea cu ap trebuie s e oprit i Centrul de asisten tehnic trebuie contactat imediat b veri ca i periodic ca presiunea de lucru a instala iei hidraul...

Page 48: ...b Trebuie avute n vedere spa iile necesare pentru accesul la dispozitivele de siguran i de reglare i pentru efectuarea opera iunilor de ntre inere b Asigura i v c gradul de protec ie electric al centr...

Page 49: ...de sus inere central termic F asigura i v c toate m surile sunt exacte apoi g uri i peretele utiliz nd un perforator care s aib v rful cu diametrul indicat anterior xa i placa cu cadrul integrat G pe...

Page 50: ...p C cu camer etan deci trebuie sa aib o conexiune sigur la conducta de evacuare a gazelor de ardere i la tubul de absorb ie a aerului pentru ardere am ndou cu ie ire la exterior i f r de care aparatul...

Page 51: ...d me najer iar lungimea maxim care poate atins este de 2 m pentru eava de 50 11 m pentru eava de 60 i 53 m pentru eava de 80 35 KIS 6 900 rot min n modul de nc lzire i 7 800 n modul de ap cald me naje...

Page 52: ...ie de umplere trebuie efectuat prin rotirea robinetului de umplere B cu centrala termic OPRIT Observa ie de ecare dat c nd centrala termic este alimentat se efectueaz ciclul automat de aerisire Obser...

Page 53: ...torului va a a urm toarele set ri Diferitele set ri disponibile vor ap rea ntr o secven ciclic Dac butonul A nu este ap sat va salvat ultima setare 2 s 2 s impostazione visualizzazione impostazione vi...

Page 54: ...indic starea sistemului semnifica ia acestora fiind urm toarea Afi ajul panoului de comand REC10 este echipat cu noua Bar colorat care informeaz rapid utilizatorul cu privire la func ionarea centralei...

Page 55: ...RE TERMOSTAT TERMOSTAT SONDA TEMPERATURA REC10 MASTER REC10 SLAVE 1 7 1 INSTALATORULUI ADRESA BE16 1 6 1 7 1 INSTALATORULUI Numai RQH FX 21 5 BE16 CONF HIDRAULICA ZONA DIRECTA ZONA DIRECTA ZONA AMESTE...

Page 56: ...ARAMETRI 1 7 1 INSTALATORULUI OPRIRE INCALZIRE 3 min 0 min 20 min 1 7 1 INSTALATORULUI HIST ON TEMP INALTA 5 C 2 C 10 C SERVICE HIST OFF TEMP INALTA 5 C 2 C 10 C SERVICE HIST ON TEMP JOASA 3 C 2 C 10...

Page 57: ...1 7 1 INSTALATORULUI DF 621 7 51 HVWH FRQHFWDW WLS VROLFLWDUH 7 L WLS RQ 7 2 0 0 1 5 0 1 7 1 INSTALATORULUI DF WLSXO GH VROLFLWDUH HVWH 621 0 17 VDX REC10 INFLUENTA AMBIENT 10 0 20 1 7 1 INSTALATORUL...

Page 58: ...curs RESETARE S GAZE ARSE 1 7 1 INSTALATORULUI ADAUGATI BOILER 1 7 1 INSTALATORULUI 1XPDL vQ FD XO FRQ JXUD LHL instantanee BOILER 1 7 1 INSTALATORULUI ELIMINATI BOILER 1 7 1 INSTALATORULUI SETPOINT...

Page 59: ...UTILIZATI CONTACTE SERVICE ACTIVATI RACIREA DEZACTIVATI RACIREA DEZACTIVATI FUNCTIA FUNCTIE ACTIVA DEZACTIVATI FUNCTIA 1 7 1 INSTALATORULUI UTILIZATI PENTRU ACM NU UTILIZ PENTRU ACM ACM FUNCTIE INACT...

Page 60: ...IA DEZACTIVATI FUNCTIA ACTIVATI FUNCTIA 1 7 1 INSTALATORULUI DEZACTIVATI FUNCTIA 1 7 1 INSTALATORULUI ACTIVATI FUNCTIA 1 7 1 INSTALATORULUI FUNCTIE SETARI SERVICE TF MIN 20 C 15 C 30 C SERVICE TF MAX...

Page 61: ...ie a aerului func ioneaz corect condi iile de ntre inere regulat sunt garantate dac centrala termic este amplasat n interiorul sau ntre elementele de mobilier etan area sistemului de admisie carburant...

Page 62: ...timpul de nt rziere introdus pentru reaprinderea arz torului fa de cel oprit pentru a atinge temperatura pentru nc lzire Setarea din fabric pentru acest parametru este de 3 minute i poate fi setat la...

Page 63: ...GESTIONARE ZONE i ZONE MODIFICATION MODIFICARE ZON cu ajutorul tastelor SUS i JOS i confirma i selec ia PARAMETRI TERMOREGLARE INSTALARE RANGE RATED CALIBRARE TEHNIC INSTALATOR CALIBRARE SENZOR MANAG...

Page 64: ...conexiunile specifice de pe placa cu borne a centralei termice n acest fel este activat func ia de TERMOREGLARE Temperatura m surat de c tre senzorul de temperatur exterioar este afi at pe pagina ini...

Page 65: ...intrarea TERMOSTAT DE CAMER din func ia TEHNIC TERMOREGLARE CURBE CLIMATICE PRINCIPAL func ia NIVEL COMPENSARE NOAPTE poate fi activat n acest caz c nd CONTACTUL este NCHIS solicitarea de nc lzire est...

Page 66: ...peraturii apei de nc lzire f r un senzor de temperatur exterioar conectat Dac nu este conectat o sond extern centrala lucreaz la punct fix n acest caz punctul de referin NC LZIRE poate fi setat select...

Page 67: ...le de defec iune i pentru a reseta centrala termic consulta i capitolul Semnaliz ri i anomalii E010 APASATI OK PENTRU RESETARE BLOCARE FLACARA 5 9 Func ia de deblocare n cazul unei bloc ri este posibi...

Page 68: ...utea efectua verificarea arderii OPRIT VARA IARNA CENTRALA 5 12 Transformarea tipului de gaz Conversia de la un tip de gaz la altul este simpl i se poate face i cu centrala instalat Aceast opera iune...

Page 69: ...belul cu date tehnice NU EXECUT I REGL RI ALE SUPAPEI DE GAZ solicita i ajutor de la Centrul de asisten tehnic b Supapa de gaz NU necesit reglare iar orice interven ie asupra acesteia determin func io...

Page 70: ...posibil s reveni i la ecranul principal unde o defec iune este semnalizat de pictograma intermitent 1 3 bar 42 C MENIU STARE SET INFO CENTRALA TEMPERATURA APA CALDA VIN 18 05 2013 12 17 Este posibil...

Page 71: ...0 Centrala termic func ioneaz normal dar nu asigur stabilitatea temperaturii apei calde menajere care n orice caz este furnizat la o temperatur de aproximativ 50 C Este necesar interven ia Centrului d...

Page 72: ...omunica ie MAGISTRALA 485 pierdut tranzi ie Lista defec iunilor de ardere COD EROARE CULOARE AFI AT MESAJ DE EROARE DESCRIEREA TIPULUI DE ALARM E021 Ro u alarm ion Acestea sunt alarme temporare care d...

Page 73: ...lzire anti nghe aceast func ie este activat dac temperatura m surat de senzorul pe tur scade sub 5 C O solicitare de nc lzire este generat n aceast faz cu aprinderea arz torului la putere minim care...

Page 74: ...ecta i op iunile dorite cu tastele SUS i JOS confirm nd selec ia APASATI O TASTA PENTRU A CONTINUA REC10R R02 06 Welcome at home Selectare LIMB ENGLISH ROM N ROMANA ENGLISH ITALIANO setarea OR i DAT I...

Page 75: ...de asisten tehnic La nlocuirea REC10 MASTER la repornirea ulterioar se afi eaz un ecran ini ial cu revizia firmware ului Ap s nd ENTER INTRODUCERE ncepe o procedur ghidat pentru configurarea sistemulu...

Page 76: ...via a centralei termice Permite reducerea consumului emisiile poluante i men inerea abilit ii produsului n timp nainte de a ncepe opera iile de ntre inere nchide i robinetele pentru combustibil i ap...

Page 77: ...stecare av nd grij s nu deteriora i panoul ceramic i electrozii n acest moment continua i cu opera iunile de cur are a arz torului Cur a i arz torul cu o perie cu peri moi av nd grij s nu deteriora i...

Page 78: ...a E nlocui i arz torul Monta i la loc arz torul n sens invers descrierii pentru demontare amintindu v s introduce i garnitura corespunz toare Demontarea ventilatorului i supapei de amestecare Fig 27 D...

Page 79: ...t pictogram indic faptul c nc lzirea instala iei zona principal este n modul MANUAL gestionarea cererilor de nc lzire nu urmeaz programarea orar setat dar este activ ntotdeauna STINS Aceast pictogram...

Page 80: ...a modurile de func ionare CENTRAL TERMIC i ZON PRINCIPAL Pentru a face acest lucru este necesar s eviden ia i intrarea dorit folosind tastele sus i jos i apoi ap sa i ok pentru a con rma selectarea Ap...

Page 81: ...punctului de setare selecta i CONFIRMARE sau ANULARE folosind tastele sus i jos i confirma i selectarea ap s nd ok Odat ce selectarea este confirmat afi ajul revine la ecranul SETARE Dac selectarea e...

Page 82: ...N AN i ap sa i tastele sus i jos pentru a modi ca valorile dorite Odat ce secven a s a terminat ap s nd ok set rile vor salvate i a ajul va reveni la ecranul ini ial Prin ap sare pe napoi n orice mome...

Page 83: ...te ora de oprire i ap sa i ok pentru a con rma selectarea 07 30 15 00 08 30 11 30 13 30 18 30 14 00 22 30 START PRINCIPAL JOI UTILIZATI SAGETILE PENTRU MODIFICARE CONFIRMA ADAUGA ORA DE SFARSIT PERIOA...

Page 84: ...punz toare i con rma i o ap s nd ok Pentru a con rma c opera ia a fost terminat cu succes pe ecran se va a a tabelul cu intervalul de timp selectat intermitent chiar nainte de a l terge din tabel 07 3...

Page 85: ...ce este oprit E094 ardere incomplet PORNIT E095 ardere incomplet PORNIT E058 defec iune tensiune re ea PORNIT Acestea sunt defec iuni temporare care restric ioneaz ciclul de aprindere E065 alarm modul...

Page 86: ...a scade frecvent contacta i Centrul de Asisten Tehnic A Pentru anomalia E091 Centrala termic are un sistem de auto diagnosticare care pe baza num rului total de ore n anumite condi ii de func ionare p...

Page 87: ...ment la ardere 97 8 97 6 97 7 E cien util Pn max Pn min 50 30 106 2 105 8 106 0 104 7 106 9 104 7 E cien util la 30 Pn max 30 retur 108 4 108 1 108 2 E cien la valoare nominal P medie 80 60 97 3 97 0...

Page 88: ...de evacuare a gazelor arse Diametru mm 60 100 60 100 60 100 Lungime maxim m 10 6 6 Pierdere la introducerea unui cot de 45 90 m 1 3 1 6 1 3 1 6 1 3 1 6 Gaur de traversare perete diametru mm 105 105 10...

Page 89: ...r rota ii ventilator aprindere lent rot min 5 500 5 500 Num r maxim de rota ii ventilator pentru nc lzire rot min 5 800 5 600 Num r maxim de rota ii ventilator ACM rot min 6 900 6 700 Num r minim de...

Page 90: ...lele cu condensare 30 C pentru centralele de joas temperatur 37 C pentru alte echipamente de nc lzire 50 C Family Cx 25 KIS Clasa de e cien energetic sezonier pentru nc lzire A Clasa de e cien energet...

Page 91: ...gimdetemperatur sc zut 1 97 5 Consumelectricauxiliar Al iparametri Lasarcin maxim elmax 28 0 W Pierderidec ldur nmodul and by P by 32 0 W Lasarcin par ial elmin 14 0 W Consumenergetical c riipilot Pig...

Page 92: ...5 Heating return line 36 Cold water Fig 1 22 9 19 6 17 32 32 33 33 34 34 35 35 36 36 25 KIS 30 35 KIS RO Elemente func ionale ale centralei 1 Robinet de umplere 2 Sifon 3 Supap de evacuare 4 Traductor...

Page 93: ...A marrone blu 5 3 1 2 4 X4 Fig 2 EN Multiwire wiring diagram L N POLARITY IS RECOMMENDED Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey G...

Page 94: ...20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 Fig 3 EN Residual head of circulator The residual head for the heating system is represented in graphic 1 according to the ow rate The piping on...

Page 95: ...circula ie de 5 metri GR 3 5 BG 3 5 EN graphic 4 setted to 4 metre circulator FR graphique 4 r gl sur un circulateur de 4 m tres HU 4 gra kon 4 m teres keringtet szivatty hoz RO gra cul 4 setare pent...

Page 96: ...s RO Instala ie la interior GR BG EN Outdoor installation in a partially protected place FR Installation l ext rieur dans un endroit partiellement prot g HU K lt ri felszerel s r szben v dett helyen...

Page 97: ...1c Fig 12 Fig 9a Fig 9b T A EN A SRD device FR A dispositif SRD HU A SRD eszk z RO A dispozitiv SRD GR A SRD BG A SRD S 3 4 1 2 3 4 1 2 F G V V1 V1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 A...

Page 98: ...0 G an instalat n mod standard GR H 90 G BG H 90 G EN H 90 bend G ange installed as standard FR H coude 90 G bride install e de s rie HU H 90 k ny k G a karima alapfelszerelts gk nt felszerelve RO H c...

Page 99: ...A co pentru conducte 50 mm sau 60 mm sau 80 mm B lungime C coturi la 90 80 mm D Reducere de la 80 la 60 mm sau de la 80 la 50 mm E Cot de 90 50 mm 60 mm sau 80 mm HU A k m ny b lel shez 50 mm vagy 60...

Page 100: ...aximum f t si h m rs klet alap rt ke jumper 1 poz nincs beiktatva T45 Padl f t s rendszerek maximum f t si h m rs klet alap rt ke jumper 1 poz beiktatva RO A GRAFICUL 1 CURBE DE TERMOREGLARE B GRAFICU...

Page 101: ...ube d aspiration d air m HU A f stg z cs hossz m B l gbesz v cs hossza m GR A m B m RO A lungime co de gaze arse m B lungime eav de aspira ie aer m BG m B m Fig 21 0 5 10 15 20 25 30 35 40 45 50 55 60...

Page 102: ...102 FAMILY CX A B C Fig 22 Fig 24 Fig 26 Fig 25 Fig 27 Fig 23 D W D E D A C B...

Page 103: ...103 FAMILY CX Fig 28 Fig 29a Fig 29c Fig 29e Fig 29b Fig 29d A F F B D C C E EN F gripper position FR F position de la pince HU F fog helyzet RO F pozi ia cle telui GR F BG F...

Page 104: ...m C a acestei centrale termice a fost reglat la _____ kW echivalent cu tura ia maxim a ventilatorului de C _____ rot min Data___ ____ ____ Semn tura _____________________ Num r de serie central termic...

Reviews: