15
ENGLISH
DEFAULT VALUE
FACTORY SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCES
LEVEL NOTES
SET
VALUE
ANTI FREEZE DELTA SET
1 °C
0 °C
6 °C
SERVICE
ENABLE NIGHT REDUCT /
DISABLE NIGHT REDUCT
DEACTIVATE
FUNCTION
FUNCTION
ACTIVE
DEACTIVATE
FUNCTION
INSTALLER
REDUCED FREQUENCY
100 %
50 %
100 %
SERVICE
MIN OUTDOOR TEMP
5 °C
-5 °C
20 °C
INSTALLER
MIN DHW OUT TEMP
5 °C
-5 °C
20 °C
INSTALLER
MIN EMERG OUT T
-10 °C
-20 °C
10 °C
INSTALLER
BOILER INTEGR DELAY
30 min
1 min
240 min
SERVICE
HP INTEGR DELAY
30 min
1 min
240 min
SERVICE
BOILER WAITING
2 min
1 min
60 min
SERVICE
HEAT PUMP WAITING
2 min
1 min
60 min
SERVICE
INTEGRATION OFFSET
5 °C
0 °C
10 °C
SERVICE
WINTER SUMMER DELAY
0h
0h
24h
SERVICE
WARNING VALIDATION
60 sec
1 sec
300 sec
SERVICE
ENABLE CIRC AUTO
MODE / ENABLE CIRC ON
MODE
AUTO
ON
AUTO
INSTALLER
DHW HP SETPOINT
60 °C
20 °C
60 °C
SERVICE
DHW OFFSET
10 °C
0 °C
25 °C
SERVICE
ENABLE ERROR HISTORY
SERVICE
ERROR HISTORY
INSTALLER
SCREED HEATING
DEACTIVATE
FUNCTION
DEACTIVATE
FUNCTION
ACTIVATE
FUNCTION
INSTALLER
DEACTIVATE FUNCTION
INSTALLER
ACTIVATE FUNCTION
INSTALLER
FUNCTION SETTINGS
SERVICE
TFMIN
20 °C
15 °C
30 °C
SERVICE
TFMAX
35 °C
30 °C
55 °C
SERVICE
COMBUSTION MONITORING
SERVICE
GAS TYPE
NATURAL GAS
NATURAL GAS / LPG
SERVICE
BOILER TYPE
A
A / B / C
SERVICE
COMBUSTION OFFSET
RESTORE
RESTORE
RESTORE
SERVICE
SYSTEM INFO
SERVICE