16
FAMILY CX
4.1
Access to the technical parameters
Through the REC10 it is possible to access, using the TECHNICAL menu,
a series of parameters that can be programmed to allow you to personalise
the operation of the boiler:
- select MENU on the main page of the REC10 and press "
ENTER
"
30
°C
.3
MENU
STATE
SET
INFO
PLANT
AIR PURGING CYCLE
FRI
1.3
bar
18/05/2013
12:17
- keep the “
BACK
” and “
DOWN
” keys pressed at the same time to enter
the password menu (about 5 sec)
MENU
SETTINGS
SELECT OPTION
FRI
18/05/2013
12:17
- with the “
UP
” and “
DOWN
” keys select the password to access the
authorisation level INSTALLER or SERVICE, depending on the level of
the tree menu, then press “
ENTER
”
00
INSERT PASSWORD
- select TECHNICAL with the "
UP
" and "
DOWN
" keys , confirming the
selection with "
ENTER
"
SELECT OPTION
SETTINGS
TECHNICAL
MENU
- access the desired menu and change/view the parameter concerned
(see "structure of the MENU tree of the REC10").
It is possible to return to the start page at any time by keeping the
CANCEL
key pressed for at least 2 seconds.
5 COMMISSIONING
5.1
Preliminary checks
The fi rst ignition should be carried out by expert personnel from an
authorised Technical Assistance Service Centre.
Before starting up the boiler, check:
- that the data of the supply networks (electricity, water, gas) correspond
to the label data
- that the extraction pipes of the fl ue gases and the air suction pipes are
working correctly
- that conditions for regular maintenance are guaranteed if the boiler is
placed inside or between items of furniture
- the seal of the fuel adduction system
- that the fuel fl ow rate corresponds to values required by the boiler
- that the fuel supply system is sized to provide the correct fl ow rate to
the boiler, and that it has all the safety and control devices required by
current regulations
- that the circulator rotates freely because, especially after long periods of
inactivity, deposits and/or debris can prevent free rotation .
Eventual releasing of the circulator shaft
- Insert a screwdriver in the hole (1) of the circulator.
- Press (
a
) and turn the Phillips no. 2 screwdriver (
b
) until the motor shaft
is released.
Perform this operation with extreme caution to avoid damaging the
components.
a
b
1
5.2
Programming the boiler
- Position the system's master switch to the "on" position.
- If necessary set the TIME and DATE setting the HOURS, MINUTES,
DAY, MONTH and YEAR with the “
UP
” and “
DOWN
” keys, confirming
the selection.
ENTER TIME AND DATE
TIME & DATE
USE THE ARROWS TO MODIFY
12
17
18/11/2013
:
Note
: it is possible to change the TIME and DATE settings, as well as the
LANGUAGE and the duration of the back-lighting, even afterwards by
entering the MENU from the main screen and then selecting SETTINGS.
b
Each time that the boiler is powered an automatic venting cycle is
carried out lasting 4 min. To interrupt the vent cycle, carry out the
procedure explained in the section "Initial commissioning".