19
MENU
DEFAULT VALUE FACTORY
SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
SETTINGS
USER
TIME & DATE
USER
DAYLIGHT SAVINGS TIME
FUNCTION ACTIVE
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
USER
LANGUAGE
ENGLISH / ITALIANO / ...
USER
BACKLIGHT
5 min
1 min
15 min
USER
TIME SCHEDULE
USER
MAIN
USER: only if POR = 1
ZONE 1
USER: only if POR = 1 and zone
added
ZONE 2
USER: only if POR = 1 and zone
added
DHW
USER: only if PLANT
CONFIGURATION = WATER TANK
HP DHW
USER: only if HP present and
USE PER DHW active
TECHNICAL
INSTALLER
INSTALLATION
INSTALLER
ZONES MANAGER
INSTALLER
MODIFY ZONE
MAIN
MAIN / ZONE 1 / ZONE 2
INSTALLER
ACTUATION TYPE
ITRF05/boiler card
ITRF05/boiler card
BE16
INSTALLER: only MAIN zone
REQUEST TYPE
THERMOSTAT
THERMOSTAT / TEMPERAURE PROBE / REC10CH
MASTER / REC10CH SLAVE
INSTALLER
BE16 ADDRESS
--
1
6
INSTALLER: only zones with
ACTUATION=BE16
HYDRAULIC CONF
DIRECT ZONE
DIRECT ZONE
MIXING ZONE
INSTALLER: only zones with
ACTUATION=BE16
ZONE TYPE
HIGH TEMP
HIGH TEMP
LOW TEMP
INSTALLER
MIN CH SET
20°C (HT)
20°C (LT)
20°C
MAX CH SET
INSTALLER
MAX CH SET
80.5 °C (HT)
45°C (LT)
MIN CH SET
80.5 °C (HT)
45°C (LT)
INSTALLER
CHANGE NAME
INSTALLER
PI - PROPORTIONAL
5
0
99
SERVICE: only mixing zones with
ACTUATION=BE16
PI - INTEGRAL
10
0
99
SERVICE: only mixing zones with
ACTUATION=BE16
VALVE RUN
120 sec
0 sec
120 sec
SERVICE: only mixing zones with
ACTUATION=BE16
CLOSING AT POWER ON
140 sec
0 sec
240 sec
SERVICE: only mixing zones with
ACTUATION=BE16
OUTLET OVER
55°C
0°C
100°C
SERVICE: only LT zones with
ACTUATION=BE16
OUTLET OVER TEST TIME
0 min
0 min
240 min
SERVICE: only LT zones with
ACTUATION=BE16
OUTLET OVER WAIT TIME
2 min
VALVE RUN
240 min
SERVICE: only LT zones with
ACTUATION=BE16
OUTLET OVER REST TIME
2 min
0 min
240 min
SERVICE: only LT zones with
ACTUATION=BE16
FREEZE PROT TEMP
6°C
-10°C
50°C
SERVICE: only zones with
ACTUATION=BE16
FREEZE PROT OFFSET
5°C
1°C
20°C
SERVICE: only zones with
ACTUATION=BE16
FREEZE PROT T EXT
10°C
0°C
100°C
SERVICE: only zones with
ACTUATION=BE16
POR
0 (1 if REC10 in the AMBIENT)
0
1
INSTALLER
ADD ZONE
INSTALLER
DELETE ZONE
INSTALLER
SENSOR CALIBRATION
0.0°C
- 6.0°C
6.0°C
INSTALLER
SYSTEM RESET
INSTALLER
PARAMETERS
INSTALLER
ANTI-CYCLE FUNCTION
3 min
0 min
20 min
INSTALLER
HYST ON HIGH TEMP
5°C
2°C
10°C
SERVICE
HYST OFF HIGH TEMP
5°C
2°C
10°C
SERVICE
HYST ON LOW TEMP
3°C
2°C
10°C
SERVICE
HYST OFF LOW TEMP
3°C
2°C
10°C
SERVICE
SP INCR HIGH TEMP
5°C (0°C if instantaneous boiler)
0°C
10°C
SERVICE
SP INCR LOW TEMP
0°C
0°C
6°C
SERVICE
3.1 Structure of the REC10CH MENU