22
MENU
DEFAULT VALUE FACTORY
SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
BOOSTER DELAY
30min
1 min
60 min
INSTALLER
BOOSTER DELTA TEMP
5°C
1°C
20°C
INSTALLER
OAT SENSOR TYP
0
0
3
INSTALLER
MINIMUM PUMP SPEED
19%
19%
100%
INSTALLER
MAXIMUM PUMP SPEED
100%
19%
100%
INSTALLER
ENABLE ERROR HISTORY
SERVICE
ERROR HISTORY
INSTALLER
SCREED HEATING
DEACTIVATE FUNCTION
DEACTIVATE FUNCTION
ACTIVATE FUNCTION
INSTALLER: OFF state and
low temperature system
DEACTIVATE FUNCTION
INSTALLER
ACTIVATE FUNCTION
INSTALLER
FUNCTION SETTINGS
SERVICE
TFMIN
20 °C
15 °C
30 °C
SERVICE
TFMAX
35 °C
30 °C
55 °C
SERVICE
COMBUSTION MONITORING
SERVICE
GAS TYPE
NATURAL GAS
NATURAL GAS / LPG
INSTALLER
BOILER TYPE (*)
A
A / B / C / .....
SERVICE
COMBUSTION OFFSET
RESTORE
RESTORE
RESET
SERVICE
ACC AUTO CAL
RESTORE
RESTORE
RESET
SERVICE
BOILER
INSTALLER
REMOVE BOILER
INSTALLER
HYDRAULIC CONFIG
1
0
4
INSTALLER
0 = system boiler (heating only boiler) / 1 =
combination boiler (instantaneous) with fl owswitch
/
2 =
combination boiler (instantaneous) with fl owmeter (Flux meter)
/ 3 = system boiler & cylinder
with probe / 4 = system boiler & cylinder with thermostat
SYSTEM INFO
SERVICE
(*) BOILER TYPE: see “6.17 COMBUSTION PARAMETERS”