background image

26

This appliance must be installed by a competent person in 

accordance with and defined by, the Standard Specification 

(Domestic Gas Installations) Declaration (I.S. 813).

4A.1  RELATED DOCUMENTS

The installation of this boiler must be in accordance with the 

relevant requirements of the local building regulations, the current 

ETCI National Rules for Electrical Installations, and the bylaws of 

the local water undertaking. It should be in accordance also with 

any relevant requirements of the local and/or district authority.

ATTENTION

The use of PPE (Personal Protective Equipment) such as but not 

limited to gloves, mask, safety glasses, etc. is strongly recom-

mended whenever carrying out the installation, repair, or mainte-

nance of this appliance – please pay particular attention to:

•  Sharp edges that may be encountered when:- handling or 

lifting the appliance, removing parts, etc. during installation 

and maintenance

• 

Airborne particles that may be released and/or disturbed when 

cleaning or removing components during maintenance

•  Water treatment chemicals that could have been added to 

the system water may spill from the appliance and or com-

ponents during maintenance

Please refer to an appropriate Health and Safety document 

such as HSE L23 (UK) or S.I. 299 (Ireland), for more detailed 

advice on safe working practices and procedures. 

4A.2  LOCATION OF APPLIANCE

The appliance may be installed in any room or internal space, 

although particular attention is drawn to the requirements of 

the current ETCI National Rules for Electrical Installations, and 

I.S. 813, Annex K. When an appliance is installed in a room 

or internal space containing a bath or shower, the appliance 

or any control pertaining to it must not be within reach of a 

person using the bath or shower. The location chosen for the 

appliance must permit the provision of a safe and satisfactory 

flue and termination. The location must also permit an adequate 

air supply for combustion purposes and an adequate space for 

servicing and air circulation around the appliance. Where the 

installation of the appliance will be in an unusual location special 

procedures may be necessary, refer to I.S. 813 for detailed 

guidance on this aspect. A compartment used to enclose the 

appliance must be designed and constructed specifically for this 

purpose. An existing compartment/cupboard may be utilised 

provided that it is modified to suit

.

This appliance is not configured for external installation

.

4A.3  GAS SUPPLY

The gas meter – as supplied by the gas supplier – must be 

checked to ensure that it is of adequate size to deal with 

the maximum rated input of all the appliances that it serves. 

Installation pipes must be fitted in accordance with I.S. 813

.

Pipe work from the meter to the appliance must be of adequate 

size.  Pipes of a smaller size than the appliance gas inlet 

connection must not be used. The installation must be tested 

for soundness in accordance with I.S. 813. 

If the gas supply serves more than one appliance, it must 

be ensured that an adequate supply is maintained to each 

appliance when they are in use at the same time.

NOTE:

 It is recognised that ‘pressure loss’ through the 

gas cock and gas valve may result in a pressure drop of 

approximately 2mbar between the gas meter and gas valve 

inlet test point; this will not impair the performance of the 

appliance, provided that a dynamic pressure of 18mbar is 

available at the appliance inlet.

4A.4  FLUE SYSTEM

The terminal should be located where the dispersal of combustion 

products is not impeded and with due regard for the damage 

and discoloration that may occur to building products located 

nearby. The terminal must not be located in a place where it is 

likely to cause a nuisance (see I.S. 813).

In cold and/or humid weather, water vapour will condense 

on leaving the terminal; the effect of such pluming must be 

considered.

If installed less than 2m above a pavement or platform to 

which people have access (including balconies or flat roofs) 

the terminal must be protected by a guard of durable material. 

The guard must be fitted centrally over the terminal. Refer to 

I.S. 813, when the terminal is 0.5 metres (or less) below plastic 

guttering or 1 metre (or less) below painted eaves.

4A. SECTION - GENERAL REQUIREMENTS (EIRE)

4A.5  AIR SUPPLY

The following notes are intended for general guidance only.

This appliance is a room-sealed, fan-flued boiler, consequently it 

does not require a permanent air vent for combustion air supply.

When installed in a cupboard or compartment, ventilation for 

cooling purposes is also not required.

4A.6  WATER CIRCULATION

Specific recommendations are given in I.S. 813. The following 

notes are for general guidance only.

4A.6.1 PIPEWORK

It is recommended that copper tubing be used in conjunction 

with soldered capillary joints.  Where possible pipes should 

have a gradient to ensure air is carried naturally to air release 

points and that water flows naturally to drain cocks

. Except 

where providing useful heat, pipes should be insulated to avoid 

heat loss and in particular to avoid the possibility of freezing. 

Particular attention should be paid to pipes passing through 

ventilated areas such as under floors, loft space, and void areas

.

4A.6.2 AUTOMATIC BY-PASS

The appliance has a built-in automatic by-pass, consequently there 

is no requirement for an external by-pass, however the design 

of the system should be such that it prevents boiler ‘cycling’.

4A.6.3 DRAIN COCKS

These must be located in accessible positions to facilitate 

draining of the appliance and all water pipes connected to the 

appliance.

4A.6.4 AIR RELEASE POINTS

These must be positioned at the highest points in the system 

where air is likely to be trapped. They should be used to expel 

trapped air and allow complete filling of the system

.

4A.6.5 EXPANSION VESSEL

The appliance has an integral expansion vessel to accommodate 

the increased volume of water when the system is heated. 

Refer to the specification table for more detailed information

.

4A.6.6 FILLING POINT

A method for initial filling of the system and replacing water lost 

during servicing etc. is provided (see fig. 6). You should ensure this 

method of filling complies with the local water authority regulations

4A.6.7 LOW PRESSURE SEALED SYSTEM

An alternative method of filling the system would be from an 

independent make-up vessel or tank mounted in a position 

at least 1 metre above the highest point in the system and at 

least 5 metres above the boiler (see fig. 7

). The cold feed from 

the make-up vessel or tank must be fitted with an approved 

non-return valve and stopcock for isolation purposes. The feed 

pipe should be connected to the return pipe as close to the 

boiler as possible.

4A.6.8 FREQUENT FILLING

Frequent  filling  or  venting  of  the  system  may  be  indicative 

of a leak. Care should be taken during the installation of the 

appliance to ensure all aspects of the system are capable of 

withstanding pressures up to at least 3 bar.

4A.7  ELECTRICAL SUPPLY

The appliance is supplied for operation on 230V @ 50Hz electrical 

supply; it must be protected with a 3-amp fuse (supplied). The 

method of connection to the mains electricity supply must allow 

for complete isolation from the supply. The preferred method is 

by using a double-pole switch with a contact separation of at 

least 3mm. The switch must only supply the appliance and its 

corresponding controls, i.e. time clock, room thermostat, etc. 

Alternatively an un-switched shuttered socket with a fused 3-pin 

plug both complying with BS 1363 is acceptable.

Warning!

This appliance must be earthed.

4A.8  MOUNTING ON A COMBUSTIBLE SURFACE

The appliance can be mounted on a wall of combustible material 

without any requirement to fit any additional protective (fire-

resistant) material.

4A.9  TIMBER FRAMED BUILDINGS

I

f the appliance is to be fitted in a timber framed building, it 

should be fitted in accordance with I.S. 813 and local Building 

Regulations. The Institute of Gas Engineers publication (IGE/

UP/7) ‘Guide for Gas Installations in Timber Frame Buildings’ 

gives specific advice on this type of installation

.

Summary of Contents for 47-364-61

Page 1: ...d member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK UNICA MAX High efficiency combi boiler UNICA MAX 35C NG G...

Page 2: ...d Your UNICA MAX boiler lights electronically and does not have a pilot light In the unlikely event of a fault developing with your boiler the supply of gas to the burner will be terminated automatica...

Page 3: ...rost protection function The pump anti lock 3 way valve and frost protection function remain active This icon indicates that WINTER mode has been selected HEATING function enabled If a heating request...

Page 4: ...0 23 59 USER only if NIGHT REDUCTION active 1 MENU DEFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNC...

Page 5: ...is related to the appliance No domestic hot water parameters can be set if MAIN ZONE 1 or ZONE 2 is selected 2 6 STATE This function can be used to set these operating modes Select STATE BOILER or MA...

Page 6: ...g it compared to that automatically calculated by the electronic board you can change the COOLING setpoint by choosing the desired comfort level 5 5 within the range Then you are asked to confirm the...

Page 7: ...Pressing ok the language selection is confirmed and the display returns to the initial screen Pressing back the system returns to the SETTINGS screen without changing the system s language BACKLIGHT t...

Page 8: ...30 18 00 END 08 30 14 00 22 30 USE THE ARROWS TO MODIFY DELETE This function serves to delete a time frame already present for the selected day START MAIN THURSDAY 07 30 11 30 18 00 END 08 30 13 30 22...

Page 9: ...t exchanger temporary E099 reset attempts exhausted boiler blocked definitive not resettable water pressure low verify the system pressure temporary water pressure high check system temporary boiler b...

Page 10: ...perature measured by the flow sensor drops below 5 C A heat request is generated in this phase with the ignition of the burner at minimum output which is maintained until the outlet water temperature...

Page 11: ...re designed for use with a sealed system only consequently they are not intended for use on open vented systems This booklet is an integral part of the appliance It is therefore necessary to ensure th...

Page 12: ...is a request for DHW via a hot water outlet or tap the pump and fan are started the fan speed will modulate until the correct signal voltage is received at the control PCB At this point an ignition se...

Page 13: ...MAX 35C UNICA MAX 40C Sides 2mm Top 100mm from casing or 25mm above flue elbow whichever is applicable Bottom 100mm Front 450mm It may be necessary to remove adjacent components if component removal r...

Page 14: ...Unit Seasonal space heating energy efficiency class A A Water heating energy efficiency class A A Rated heat output Pnominal 31 31 kW Seasonal space heating energy efficiency s 94 94 Useful heat outp...

Page 15: ...SPEED CIRCULATOR WITH CONSTANT T MODE 2 DUTY CYCLE PUMP 40 In this mode the installer sets the T value to be maintained between flow and return e g by entering a value 10 the circu lator speed will ch...

Page 16: ...ning in the car port into the building 1200 mm M Vertically from a terminal on the same wall 1500 mm N Horizontally from a terminal on the same wall 300 mm P From a structure to the side of the vertic...

Page 17: ...l be flashing If there is a CH request from the additional zone the number 1 or 2 is flashing Only if heat pump is present This icon indicates that cooling is active in the SUMMER state If a cooling r...

Page 18: ...e signal on the main screen corresponds to the highest priority in the following ascending order Grey Green Yellow and Red The configuration MENU is organised with a multi access level tree structure...

Page 19: ...99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE only mixing zones with ACTUATION BE16 CLOSIN...

Page 20: ...est type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTALLER...

Page 21: ...LE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 present...

Page 22: ...N INSTALLER ACTIVATE FUNCTION INSTALLER FUNCTION SETTINGS SERVICE TFMIN 20 C 15 C 30 C SERVICE TFMAX 35 C 30 C 55 C SERVICE COMBUSTION MONITORING SERVICE GAS TYPE NATURAL GAS NATURAL GAS LPG INSTALLER...

Page 23: ...INSTALLER PUMP DUTY CYCLE INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER PARAMETERS CALIBRATION 8 FRI 09 04 2021 12 17 MENU INFO SET AIR PURGING CYCLE IN PROGRESS STATE 30 C 3 PLAN...

Page 24: ...ly serves more than one appliance it must be ensured that an adequate supply is maintained to each appliance when they are in use at the same time NOTE It is recognised that pressure loss through the...

Page 25: ...BLE SURFACE Theappliancecanbemountedonawallofcombustiblematerial without any requirement to fit any additional protective fire resistant material 4 9 TIMBER FRAMED BUILDINGS If the appliance is to be...

Page 26: ...o which people have access including balconies or flat roofs the terminal must be protected by a guard of durable material The guard must be fitted centrally over the terminal Refer to I S 813 when th...

Page 27: ...he correct way up 5 2 CONTENTS Contained within the carton is the boiler the wall bracket carton template anaccessoriespackcontainingapplianceserviceconnections and washers theinstructionpackcontainin...

Page 28: ...d an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely Once the bracket has been secured to the wall mount the appliance onto the bracket Fig 11 fla...

Page 29: ...and plugged An appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely Once the bracket has been secured to the wall mount the appliance onto the bracket...

Page 30: ...pliance Fig 18 5 6 6 COMBINED PRV CONDENSATE DISCHARGE PIPE This appliance will under normal operating conditions produce condensate fluid that will require to be disposed of via the dwelling s waste...

Page 31: ...ance UI and is set adjusted via the OT control INFO Menu When an OT control is connected the info menu will display the HW set point instead of the HW flow rate NOTE all any functions of the main zone...

Page 32: ...release the cover and then remove the cover lifting from the front upwards The 230v electrical supply input is located at the rear right hand side of the PCB see section 8 schematics disconnect and r...

Page 33: ...17 ENTER TIME AND DATE TIME DATE USE THE ARROWS TO MODIFY 18 11 2013 Note it is possible to change the TIME and DATE DAYLIGHT SAVINGS TIME settings as well as LANGUAGE and the duration of the back li...

Page 34: ...d DO_AUX1 0 additional pump management zone valve management DO_AUX1 1 zone valve management zone valve management DO_AUX1 2 additional pump management additional pump management CONFIG OTBUS this par...

Page 35: ...CTIVITY EXT SENSOR set the desired value Note The value of the calculated outdoor temperature used by the thermoregulation algorithm is displayed in the INFO menu under T EXT FOR THERMOREG HEAT REQUES...

Page 36: ...be interrupted by removing the cap from the control panel and pressing the combustion analysis button SW1 or in the following way Select TECHNICAL AIR PURGING CYCLE STOP FUNCTION INSTALLER WEATHER CO...

Page 37: ...burner will switch off and the pump will continue to run In the unlikely event of a fault or malfunction occurring the appliance will enter a temporary or final fault condition during which it shutdo...

Page 38: ...ER ONLY HEATING AND HOT WATER 1 Perform the combustion check verifying that the CO2 values correspond to those indicated in section 2 Once completed remove the analyser probe and close the combustion...

Page 39: ...ault E091 The boiler has an auto diagnostic system which based on the total number of hours in certain operating conditions can signal the need to clean the primary exchanger alarm code E091 Once the...

Page 40: ...ry the simultaneous replacement of both electronics boards AKM and REC10CH MASTER will require the re programming of these parameters Set SERVICE password Select TECHNICAL COMBUSTION MONITORING AIR PU...

Page 41: ...sate fluid b Once the operations have been completed reassem ble the components by operating in the reverse order to what is described checking the floating seal and replace it if necessary If replaci...

Page 42: ...lace Explain to the user how to isolate the appliance from the gas water and electricity supplies and the locations of all drain points Show the user how to operate the appliance and any associated co...

Page 43: ...t the internal components and electrical wiring for any defect or deterioration 4 Visually check for any dirt or debris within the condensate trap the trap is translucent and can be checked visually 5...

Page 44: ...pipe of the boiler reduce the fan speed via the electronic circuitry Depending on the load either the water temperature will continue to rise until the set point is achieved or the water temperature...

Page 45: ...disconnection and re connection of any electrical wiring or component these checks must be repeated 8 6 FAULT FINDING Before attempting any faultfinding the electrical checks as detailed in section 8...

Page 46: ...return and down arrow buttons until the display changes to show INSERT PASSWORD 3 using the up arrow button press until 18 is shown in the display then press select 4 use the following menu string ME...

Page 47: ...HS pink PWM grey F Lv X13 1 4 1 10 X19 D H W T 1 3 P T t F M 1 3 black 5Vdc blue sign brown red blue sign violet 5Vdc orange red grey grey MOD 1 X9 12 t t t F O H T R S F T F S red red white white gr...

Page 48: ...WARNING The gas supply to the appliance must remain turned OFF until the following procedure has been completed 1 Select STATE BOILER 2 Set the SERVICE password 3 Select TECHNICAL COMBUSTION MONITORI...

Page 49: ...h section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES I Is s C CO O 3 35 50 0p pp pm m a an nd d C CO O C CO O2 2 r ra at...

Page 50: ...turers recommendations at least annually This must be carried out by a competent Gas Safe registered engineer The service details should be recorded on the Benchmark Service and Interim Boiler Work Re...

Page 51: ...no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced Yes COMBINATION BOILERS ONLY Is t...

Page 52: ...eer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas...

Page 53: ...eer name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas...

Page 54: ...mmissioning sheet RGII Installation Certificate ROI the warranty will commence from the date of manufacture as detailed on the appliance data plate 6 To qualify for the full term of warranty the boile...

Page 55: ...adhered to f To any other costs or expenses caused by or arising as a result of the breakdown of a Vok ra Boiler g To any costs incurred during delays in fixing reported faults 10 We reserve the righ...

Page 56: ...Herts AL2 1HG www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Reviews: