33
ANTI-CYCLE FUNCTION
RESET CH TIMERS
DHW THERMOSTAT
PARAMETERS
INSTALLER
PRE-HEATING
-
ANTI-CYCLE FUNCTION:
once the setpoint has been
reached the burner will cycle on and off until an external
control, e.g. time clock cancels the heating request. This
function imposes a set time between the burner OFF/ON
cycles in order to optimise efficiency. The factory setting
for this parameter is 3 minutes and can be set to a value
between 0 min and 20 min selecting the desired one.
ANTI-CYCLE FUNCTION
3
MIN
-
RESET CH TIMER:
this parameter allows you to reset
the REDUCED HEATING MAXIMUM OUTPUT TIMING,
during which the speed of the fan is limited to 75% of the
maximum heating output that has been set, and the AIR
PURGING CYCLE. The factory setting for this parameter
is FUNCTION NOT ACTIVE, select FUNCTION ACTIVE,
confirming the selection for resetting the timings.
FUNCTION ACTIVE
INSTALLER
FUNCTION NOT ACTIVE
RESET CH TIMERS
-
SLIDING OUTLET (only if water tank connected):
this
parameter allows you to activate the SLIDING OUTLET
function for changing the delivery setpoint used by the boiler,
when in domestic hot water request mode. The factory value
is FUNCTION NOT ACTIVE: modulation at a fixed delivery
value of 80°C. By choosing FUNCTION ACTIVE the delivery
setpoint is no longer fixed at 80°C, but can be changed and
calculated automatically by the boiler on the basis of the
difference between the desired domestic hot water setpoint
and the temperature measured by the water tank probe. Note:
we recommend activating this function for storage cylinders
with a capacity greater than 100 litres, loading the cylinder
would be too slow.
b
It might be necessary to reset the value of this parameter
when replacing the adjustment board.
FUNCTION NOT ACTIVE
SLIDING OUTLET
FUNCTION ACTIVE
INSTALLER
-
DO_AUX1:
through this value it is possible to configure the
functions associated with the digital output used to manage
the additional pump and the zone valve. The factory setting
for this parameter is 0 and can be set within the 0 - 2 range
with the following meaning:
Pin 1 and 2 of X21 Jumper not present Jumpered
DO_AUX1 = 0
additional pump
management
zone valve
management
DO_AUX1 = 1
zone valve
management
zone valve
management
DO_AUX1 = 2
additional pump
management
additional pump
management
-
CONFIG OTBUS
: this parameter is used to enable the
remote control of the boiler via an OpenTherm device:
1 = FACTORY VALUE. OTBus function enabled. The
message “OPEN THERM CONNECTED” will appear on
the display, when an OTBus device connected.
0 = OTBus function disabled. If this parameter is set at
0, any possible OTBus connection is instantaneously
interrupted.
6.2.2 CONFIGURATION OF THE ZONE
It is possible to customise the management of the heating
zone by accessing the ZONES MANAGER menu.
- Access to menu TECHNICAL
INSTALLATION
ZONES MANAGER
MODIFY ZONE.
PARAMETERS
WEATHER COMPENSATION
INSTALLATION
RANGE RATED
CALIBRATION
INSTALLER
TECHNICAL
SENSOR CALIBRATION
ZONES MANAGER
SYSTEM RESET
INSTALLER
INSTALLATION
ADD ZONE
MODIFY ZONE
DELETE ZONE
INSTALLATION
INSTALLER
- Select the desired heating zone and then choose from
among the options:
MAIN
INSTALLER
INSTALLATION
-
TYPE OF ACTUATION:
set the parameter in question to
ITRF05/AKM (default value)
-
TYPE OF HEAT REQUEST
: this parameter allows you to
specify the type of heat request, it is possible to choose
from among the following options:
THERMOSTAT
(factory setting): the heat request is
generated with an ON/OFF thermostat
REC10 MASTER:
the heat request is generated by the
REC10 MASTER; in this case the REC10 assumes the
function of an HIU (Human Machine Interface)
-
TYPE OF ZONE:
this parameter allows you to specify the
type of zone to be heated, it is possible to choose from
among the following options:
HIGH TEMPERATURE (factory setting):
LOW TEMPERATURE
-
MIN SET HEAT:
this parameter allows you to specify the
minimum heating setpoint that is possible (range 20°C -
80.5°C, default 20°C for high temperature systems; range
20°C - 45°C, default 20°C for low temperature systems)
-
MAX SET HEAT:
this parameter allows you to specify the
maximum heating setpoint that is possible (range 20°C
- 80.5°C, default 80.5°C for high temperature systems
- range 20°C - 45°C, default 45°C for low temperature
systems)
-
CHANGING NAME:
this parameter allows you to attribute
a specific name to the heating zone
-
POR (embedded clock function):
this parameter
enables or disables the embedded clock.
Embedded clock disabled (default) = 0
Central heating is controlled (ON & OFF) by the room
thermostat connection (TA).
Embedded clock enabled = 1
Central heating ON/OFF times are controlled according to
the (default) heating programme, whilst room temperature
is controlled via the room thermostat (TA). Ensure that the
operating mode (‘STATE’ menu) is set to AUTO.
b
If you want to deactivate the zone in summer or winter, you
must select the pre-established season (SUMMER or WIN-
TER in the boiler MENU) and set the zone in question to off
in the STATE or MODE menu
.
6.2.3 ANTI-LEGIONELLA FUNCTION (only if
connected a water tank with probe)
The machine has an automatic ANTI-LEGIONELLA function
that, if necessary, heats the domestic water to 70°C and
keeps it at that temperature for 15 minutes to prevent the
proliferation of bacteria in the water tank. This function can
be set to be activated every day or every week. This function
is not performed if the water tank temperature has reached
70°C over the past 24 h - in case it is set to start daily - or over