20
MENU
DEFAULT VALUE FACTORY
SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
SP INCR LOW TEMP
0°C
0°C
6°C
SERVICE
DECR COOLING SP
0°C
0°C
10°C
SERVICE
PUMP DUTY CYCLE
85
0
100
INSTALLER
RESET CH TIMERS
FUNCTION NOT ACTIVE
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
INSTALLER
SLIDING OUTLET
DEACTIVATE FUNCTION
DEACTIVATE FUNCTION
ACTIVATE FUNCTION
INSTALLER: only in “heating only”
confi g. and water tank with probe
CH DELAY POST-DHW
0
0
1
SERVICE
CH DELAY TIME
6 sec
1 sec
255 sec
SERVICE: if CH DELAY POST-
DHW = 1
PRESS TRANSDUCER
1
0
1
SERVICE
AUTO WATER FILL ENABLE
0
0
1
SERVICE: only if PRESS
TRANSDUCER = 1
BEGIN SYSTEM FILLING
0.6
0.4
1
SERVICE: only if AUTO WATER
FILL ENABLE = 1
DO_AUX1
0
0
2
INSTALLER: only if control boards
with OTBus
CONFIG OTBUS
1
0
1
SERVICE: only if control boards
with OTBus
WEATHER COMPENSATION
INSTALLER
CLIMATIC CURVES
MAIN
MAIN / ZONE 1 / ZONE 2
INSTALLER
FIXED SET POINT
80.5 °C (HT)
45 °C (LT)
MIN CH SET
MAX CH SET
INSTALLER: if EXTERNAL
PROBE NOT connected
NIGHT COMP
FUNCTION NOT ACTIVE
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
INSTALLER: if EXTERNAL
PROBE connected
CURVE SLOPE
2.0
1.0
3.0
INSTALLER: if EXTERNAL
PROBE, request type TA and
zone type HT
0.4
0.2
0.8
INSTALLER: if EXTERNAL
PROBE, request type TA and
zone type LT
2.0
1.0
5.0
INSTALLER: if request type
AMBIENT PROBE or REC10CH
AMBIENT INFLUENCE
10
0
20
INSTALLER: if request type
AMBIENT PROBE or REC10CH
OFFSET
20°C
20°C
40°C
INSTALLER: if request type
AMBIENT PROBE or REC10CH
COOLING
18°C
4°C
20°C
INSTALLER: if COOLING CURVE
deactivated
COOLING CURVE
1
1
2
INSTALLER: if COOLING CURVE
activated
BUILDING TYPE
5 min
5 min
20 min
INSTALLER: if EXTERNAL
PROBE connected
OUTDOOR REACTIVITY
20
0
255
INSTALLER: if EXTERNAL
PROBE connected
ENABLE/DISABLE COOLING CURVE
INSTALLER: if HP present and
enable to COOLING
RANGE RATED
not used
INSTALLER
CALIBRATION
INSTALLER
MIN
see MULTIGAS TABLE
INSTALLER
MAX
see MULTIGAS TABLE
INSTALLER
RLA
see MULTIGAS TABLE
INSTALLER
MAX CH
see MULTIGAS TABLE
INSTALLER
COMBUSTION ANALYSIS
INSTALLER
ACTIVATE FUNCTION
INSTALLER
DEACTIVATE FUNCTION
INSTALLER
MAX SPEED
MAX
INSTALLER
RANGE RATED SPEED
RANGE RATED
INSTALLER
MIN SPEED
MIN
INSTALLER
CHANGE FAN SPEED
CURRENT SPEED
MIN
MAX
INSTALLER
ANTI-LEGIO
WEEKLY FUNCTION
FUNCTION NOT ACTIVE / DAILY FUNCTION / WEEKLY
FUNCTION
INSTALLER: only if “only heating”
confi g.
and water tank with probe
ANTILEGIO FLOW
80°C
65°C
85°C
INSTALLER
ANTILEGIO TIME
03:00
00:00
23:30
INSTALLER
ANTILEGIO TEMP
70°C
55°C
WATER TANK T MAX
INSTALLER
AIR PURGING CYCLE
FUNCTION DISABLED
FUNCTION DISABLED
FUNCTION ENABLED
SERVICE
FUNCTION DISABLED
SERVICE
FUNCTION ENABLED
SERVICE
STOP FUNCTION
INSTALLER: only if AIR
PURGING CYCLE in progress
EXHAUST PROBE RESET
INSTALLER
ADD WATER TANK
INSTALLER: only if instantaneous
and “only heating” confi g.
MENU
DEFAULT VALUE FACTORY
SET
MINIMUM
VALUE
MAXIMUM
VALUE
ACCESS LEVEL
NOTES
SET
VALUE
WATER TANK
INSTALLER
REMOVE WATER TANK
INSTALLER
WATER TANK TYPE
0
0
1
INSTALLER: only if “only heating”
confi guration
TANK FROST PROTECT
7°C
0°C
100°C
SERVICE: only if “only heating”
confi guration with water-tank
TANK FR PROT OFFSET
5°C
1°C
20°C
SERVICE: only if “only heating”
confi guration with water-tank
WATER TANK FLOW
80°C
50°C
85°C
INSTALLER: only if “only heating”
confi guration with water-tank
ADD SOLAR PLANT
INSTALLER: only if solar system
is not confi gured
SOLAR
INSTALLER
REMOVE SOLAR PLANT
INSTALLER
T MAX TANK
60°C
10°
130°C
INSTALLER
DELTA T ON PUMP
8°C
DELTA T OFF PUMP
30°C
INSTALLER
DELTA T OFF PUMP
4°C
4°C
DELTA T ON PUMP
INSTALLER
INTEGRATION DELAY
0 min
0 min
180 min
INSTALLER
COLLECTOR T MIN
(- -)
(- -)/-30°C
- -°C
INSTALLER
COLLECTOR T MAX
110°C
COLLECTOR T PROT
180°C
INSTALLER
COLLECTOR T PROT
110°C
80 °C
COLLECTOR T MAX
INSTALLER
COLLECTOR T AUTH
40°C
COLLECTOR T LOCK
95°C
INSTALLER
COLLECTOR T LOCK
35°C
-20°C
COLLECTOR T AUTH
INSTALLER
PWM COLL PUMP
0 min
0 min
30 min
INSTALLER
TANK COOLING
FUNCTION NOT ACTIVE
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
INSTALLER
SOLAR PUMP MODE
OFF
OFF / ON / AUTO
INSTALLER
ADD HEAT PUMP
INSTALLER: only if HP not
confi gured
HEAT PUMP
INSTALLER
ADD HEAT PUMP/REMOVE PDC
INSTALLER: only if HP and boiler
present
USE FREE CONTACTS/USE BUS
USE BUS
USE BUS
USE FREE CONTACT
SERVICE
ENABLE/DISABLE COOLING
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
FUNCTION NOT ACTIVE
INSTALLER
USE FOR DHW/DON’T USE FOR DHW
DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER: if BE17 present
ANTI FREEZE DELTA SET
1°C
0°C
6°C
SERVICE
ENABLE/DISABLE NIGHT REDUCT
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
FUNCTION NOT ACTIVE
INSTALLER
REDUCED FREQUENCY
80%
50%
100%
INSTALLER: if NIGHT
REDUCTION active
NIGHT MODE START TIME
20:00
00:00
23:59
INSTALLER: if NIGHT
REDUCTION active
NIGHT MODE STOP TIME
09:00
00:00
23:59
INSTALLER: if NIGHT
REDUCTION active
MIN OUTDOOR TEMP
5°C
-5°C
20°C
INSTALLER
MIN DHW OUT TEMP
5°C
-5°C
20°C
INSTALLER: only if USE FOR
DHW in HP activated
MIN EMERG OUT T
-10°C
-20°C
10°C and in any case not
over the MIN OUTDOOR
TEMP value
INSTALLER
BOILER INTEGR DELAY
30 min
1 min
240 min
SERVICE
HP INTEGR DELAY
30 min
1 min
240 min
SERVICE
BOILER WAITING
2 min
1 min
60 min
SERVICE
HEAT PUMP WAITING
2 min
1 min
60 min
SERVICE
INTEGRATION OFFSET
5°C
0°C
10°C
SERVICE
WINTER SUMMER DELAY
0h
0h
24h
SERVICE
WARNING VALIDATION
60 sec
1 sec
300 sec
SERVICE
ENABLE CIRC ON/AUTO MODE
AUTO
ON
AUTO
INSTALLER: if boiler in OFF and
AIR PURGING CYCLE not present
DHW HP SETPOINT
60°C
20°C
60°C
SERVICE: only if USE FOR DHW
in HP activated
DHW OFFSET
10°C
0°C
25°C
SERVICE: only if boiler with water
tank with probe and USE FOR
DHW in HP activated
ADD PHOTOVOLTAIC
INSTALLER
PHOTOVOLTAIC
INSTALLER
REMOVE PHOTOVOLTAIC
INSTALLER
ELECTRIC CONVENIENCE
2
0
+10°C
INSTALLER
BACKUP TYPE
1
0
1
INSTALLER
BOOSTER OAT THRESHOLD
-7°C
MIN EMERG OUT T
15°C
INSTALLER
BOOSTER DELAY
30min
1 min
60 min
INSTALLER