40
6.15 WATER TANK CONFIGURATION
b
The boiler leaves the factory pre-configured for manag-
ing a water tank with a thermostat (water tank type pa-
rameter = 0
).
To modify the configuration of the water tank:
-
select TECHNICAL
WATER TANK
CALIBRATION
TECHNICAL
INSTALLER
COMBUSTION ANALYSIS
EXHAUST PROBE RESET
WATER TANK
-
choose from the following options:
WATER TANK
INSTALLER
REMOVE WATER TANK
WATER TANK TYPE
WATER TANK FLOW
WATER TANK TYPE:
this parameter allows you to set the
type of the water tank. Set the value to 1 to select a water
tank with probe, set the value to 0 to select a water tank with
thermostat (factory setting).
REMOVE WATER TANK:
this function is used to disable the
operation of the water tank; water tank disabled, the relative
configuration menu is no longer accessible. If you wish to add
a storage cylinder again, after a previous removal, follow the
instructions in paragraph section 4.7.
WATER TANK FLOW:
the parameter allows you to set the
delivery temperature of the boiler to the water tank when the
SLIDING OUTLET function is not active. The factory setting
is 80°C.
6.16 TEMPORARY SWITCH-OFF
In the event of temporary absences (weekends, short breaks,
etc.) set the status of the boiler to OFF .
Refer to section 3.3 for further details.
BOILER
OFF
WINTER
6.17 SWITCHING OFF FOR LENGTHY
PERIODS
Refer to section 3.4 for detailed advice on shutting down the
appliance for an extended period of time.
BOILER
OFF
WINTER
ON
OFF
6.18 COMBUSTION PARAMETERS
Although the parameters referring to the combustion control
system ACC (Active Combustion Control) are preset in the
factory, the simultaneous replacement of
both
electronics
boards (AKM and REC 10 MASTER) will require the re-
programming of these parameters.
- Set SERVICE password
- Select TECHNICAL
COMBUSTION MONITORING
AIR PURGING CYCLE
PARAMETERS
EXHAUST PROBE RESET
ERROR HISTORY
COMBUSTION MONITORING
SERVICE
TECHNICAL
- Select GAS TYPE
- Set this parameter depending on the type of gas of the
boiler: NG = NATURAL GAS - LPG = LPG
COMBUSTION MONITORING
COMBUSTION OFFSET
BOILER TYPE
GAS TYPE
SERVICE
- Select BOILER TYPE and set as shown in the table
A
B
C
SERVICE
BOILER TYPE
...
BOILER TYPE
UNICA MAX 20S
A
UNICA MAX 30S
G
-
Select COMBUSTION OFFSET
RESTORE
-
Press OK to confirm.
COMBUSTION OFFSET
RESTORE
RESET
SERVICE
COMBUSTION SELF-CALIBRATION
Function used by the after sales service to make an automatic
combustion curve correction if the CO
2
values (shown in the
technical data) are outside the permitted range.
- Power the boiler electrically by bringing the main switch to
“ON”.
- Set the boiler status to OFF.
- Select TECHNICAL
COMBUSTION CONTROL
SELF-CALIBRATION.
- Set the values to:
RESTORE = use the old curve (if the CO
2
value is too high)
RESET = use the new curve (if the CO
2
value is too low).
This parameter is only available when the system is OFF.
6.19 MAINTENANCE
b
In case where, after the replacement of the electronic
board or the maintenance of the detection electrode or
the burner, the combustion analysis would restore out of
tolerance values, it may be necessary to take action on
the parameter COMBUSTION OFFSET as described in
the
section 6.18.
Note:
in case of replacement of the electrode, slight
variations of the combustion parameters can not be
excluded. These data wil return to nominal values after
a few hours of operation.
b
Do not clean the appliance or its parts with inflammable
substances (e.g. petrol, alcohol, etc.).
b
Do not clean panels, painted parts and plastic parts with
paint thinner.