Figure 3-8
EC integration time
3.3.1.3
EC pre-blending
EC pre-blending active
EC pre-blending setpoint
Minimum alarm zone of EC pre-blending
Maximum alarm zone of EC pre-blending
Alarm delay for EC pre-blending
Response to EC pre-blending alarm
Gain
Differentiation time
Maximum control percentage
Path: Settings>Programs>Program name>EC-pre-blending
EC pre-blending active
No: Not active.
Yes: Active.
Pre-blending EC setpoint 0 - 9.9 mS/cm
The desired EC value of the irrigation water during pre-blending.
Minimum alarm zone of EC pre-blending 0 - 9.9 mS/cm
The value in mS/cm that the 'Measured pre-blending EC' must drop below the
'Calculated EC setpoint' during pre-blending for an alarm to be triggered.
Maximum alarm zone of EC pre-blending 0 - 9.9 mS/cm
The value in mS/cm that the 'Measured pre-blending EC' must rise above the
'Calculated EC setpoint' during pre-blending for an alarm to be triggered.
Alarm delay for EC pre-blending
The duration that the measured value must continuously remain above the pre-set
maximum or below the pre-set minimum for an alarm to be triggered.
Aqua CX300
28