69
The phase detect relay will open circuit if the heat pump has been wired with
incorrect phase rotation or if a phase has failed. Both red and green LEDs on
the relay will be illuminated if phase rotation is correct.
Alarm light on heat pump controller
If the alarm light is flashing RED, check the alarm by pressing the alarm
button. Phone your nearest Rheem Service Department or Accredited
Service Agent (or Service Centre in NZ) to inform about the alarm.
Activation of Freeze Protection
Check the control panel of the heat pump. Read the error message/ warning
if it shows on the display.
Heat pump starts then turns off soon after
This could be caused by:
a. Insufficient water flow rate through heat exchanger. Check pipe sizing
per chart, check obstructions, check lines and pump are bled, check
pump is operating.
Note:
Tanks and heat pumps are to be manifolded in Equa-Flow. It is
important that the branches to each storage tank
ONLY
contain a gate or
ball valve and union. Fitting of loose jumper valves, non-return valves or
pressure limiting valves in the branches or primary flow and return lines
between the heat pump and tanks
WILL
affect performance of the heat
pump.
b. Refrigerant charge too high
c. Refrigerant charge too low?
Turn heat pump off then on again at isolating switch to reset system.
Heat pump compressor excessively noisy
Check for correct phase rotation (refer to
Summary of Contents for W2W Series
Page 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Page 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Page 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Page 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Page 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Page 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Page 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Page 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...