The commissioning procedure
MUST
be performed in the order shown.
1.
Ensure all heat pumps are turned OFF at the isolating switch.
2.
Turn ON slave 1 heat pump (2
nd
heat pump).
3.
Configure heat pump address.
Whilst in the home screen on control panel, simultaneously press and hold
Up
, Down
and Enter
for 5 seconds to enter the setup menu.
Use Up
or Down
buttons to set values.
Press and release Enter
to move curser to next line.
Change the following values as shown below.
Menu
Slave 1
Slave 2
Slave 3
Master
Example Screen Image of Slave 1
Display
address
setting
17
18
19
16
I/O board
address
02
03
04
01
trm1
32
32
32
32
trm2
17
18
19
16
trm3 None
– Ok?
Yes
Yes
Yes
Yes
Press “Enter”
to confirm settings. The screen will change to the home
screen and settings will be saved.
1
st
Heat Pump- Master
2
nd
Heat Pump
3
rd
Heat Pump
4
th
Heat Pump
Summary of Contents for W2W Series
Page 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Page 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Page 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Page 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Page 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Page 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Page 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Page 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...