CONNECTIONS - ELECTRICAL
55
f.
Service Settings
a. Working Hour Set
b. Prove Adjustment
c. Thermoregulation (for multiple heat pump installation,
change the no. of compressor and other settings from here.)
f. Service Settings Screen
Parameter
Sub Parameter
Master
Slave
c. Thermoregulation
Thermoregulation 01
Setpoint
60.0°C
Screen N/A
Differential
3.0°C
Screen N/A
Dead band
0.5°C
Screen N/A
Thermoregulation 02
(De-ice temp)
(4)
Initiate
-4°C
-4°C
Terminate
10.0°C
10.0°C
Thermoregulation 03
(De-ice timers)
(4)
Delay to start
5m
5m
Max duration
15m
15m
Min between
30m
30m
Coil de-water
30s
30s
Thermoregulation 04
(Pump settings)
Flow proof delay
3s
Screen N/A
Pump min run
5m
Screen N/A
Pump run on time
1m
Screen N/A
Temp. test cycle
Not avail
Screen N/A
Flow switch fitted
Yes
Screen N/A
Thermoregulation 05
Blackout delay
10s
Screen N/A
No of compressors
Set as required
(default 1)
Screen N/A
Compressor staging
Simultaneous
Screen N/A
Controlling sensor
Tank
Screen N/A
I/O Config 05
Out air sensor
No
No
Sensor type
Carel NTC
Carel NTC
Thermoregulation 06
(Enable unit On/Off)
By digital input
No
Screen N/A
By supervisor
No
Screen N/A
By flow switch
No
Screen N/A
Dig input 6 is for
Comp O/Load
(4)
Screen N/A
I/O Config 06b
Storage tank temp
Yes
No
Sensor type
Carel NTC
Carel NTC
Building flow temp
Yes
No
Sensor type
Carel NTC
Carel NTC
Thermoregulation 07
(HP/LP Safety)
LP trip set
0.1 Bar
0.1 Bar
HP trip set
27.5 Bar
27.5 Bar
Thermoregulation 08
(Anti-freeze safety for
PHE evaporator leave)
Low limit set
5.0ºC
Screen N/A
Thermoregulation 09
Aux. Boost Fitted:
Yes
Screen N/A
% compressor in
alarm to activate
boost
50 %
Screen N/A
Boost. act. Delay
5m
Screen N/A
Thermoregulation 10
(Low outside air temp)
(4)
Cut over point
5.0ºC
Screen N/A
Differential
2.0ºC
Screen N/A
Comp stop in low
outside air temp:
No
Screen N/A
(1)
Parameter only available where
'H. Manufacturer > Configuration 01 > No. Compressors'
= 2, 3 or 4.
(2)
Parameter only available where
'H. Manufacturer > Configuration 01 > No. Compressors'
= 3 or 4.
(3)
Parameter only available where
'H. Manufacturer > Configuration 01 > No. Compressors'
= 4.
(4)
Component is not present for W2WHP and should be ignored.
d. User DEV/Change PW1
For more information, please refer to the service manual for heat pumps
.
Summary of Contents for W2W Series
Page 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Page 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Page 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Page 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Page 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Page 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Page 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Page 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...