63
BMS
Address
Description
Default
Category UOM
Min
Max
Read/Write
Variable name
30
Water Setpoint
22.0
Default
°C
5.0
45.0
R/W
Setpoint
31
Dead band
1.0
Default
°C
0
9.9
R/W
D_Band
32
Proportional Band for compressor
1.5
Default
°C
0
25.0
R/W
Pro_band
33
Entering water temperature 2
0
Default
°C
-99.9
99.9
R
EW_temp2
34
Leaving water temperature 2
0
Default
°C
-99.9
99.9
R
LW_temp2
35
Storage tank water temperature
0
Default
°C
-99.9
99.9
R
Tank_temp
36
Building Supply water temperature
(Flow)
0
Default
°C
-99.9
99.9
R
Bld_Supply_temp
Integer variables
BMS
Address
Description
Default
Category UOM
Min
Max
Direction
Variable name
21
type of tariff - timeband 0 week end
0
Default
---
0
2
R/W
trfw_0
22
type of tariff - timeband 1 week end
0
Default
---
0
2
R/W
trfw_1
23
type of tariff - timeband 2 week end
0
Default
---
0
2
R/W
trfw_2
24
type of tariff - timeband 3 week end
0
Default
---
0
2
R/W
trfw_3
25
type of tariff - timeband 4 week end
0
Default
---
0
2
R/W
trfw_4
26
type of tariff - timeband 5 week end
0
Default
---
0
2
R/W
trfw_5
27
type of tariff - timeband 6 week end
0
Default
---
0
2
R/W
trfw_6
28
type of tariff - timeband 7 week end
0
Default
---
0
2
R/W
trfw_7
29
type of tariff - timeband 8 week end
0
Default
---
0
2
R/W
trfw_8
30
type of tariff - timeband 9
0
Default
---
0
2
R/W
trfw_9
31
type of tariff - timeband 10 week end
0
Default
---
0
2
R/W
trfw_10
32
type of tariff - timeband 11 week
end
0
Default
---
0
2
R/W
trfw_11
33
type of tariff - timeband 12 week end
0
Default
---
0
2
R/W
trfw_12
34
type of tariff - timeband 13 week
end
0
Default
---
0
2
R/W
trfw_13
35
type of tariff - timeband 14 week end
0
Default
---
0
2
R/W
trfw_14
36
type of tariff - timeband 15 week
end
0
Default
---
0
2
R/W
trfw_15
37
type of tariff - timeband 16 week end
0
Default
---
0
2
R/W
trfw_16
38
type of tariff - timeband 17 week
end
0
Default
---
0
2
R/W
trfw_17
Summary of Contents for W2W Series
Page 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Page 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Page 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Page 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Page 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Page 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Page 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Page 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...