INSTALLATION
THIS WATER HEATER IS FOR INDOOR OR OUTDOOR INSTALLATION.
THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING.
INSTALLATION STANDARDS
The water heater must be installed:
by a qualified person, and
in accordance with the installation instructions, and
in compliance with Standards AS/NZS 3500.4, AS/NZS 3000 and all local
codes and regulatory authority requirements.
In New Zealand, the installation must also conform with Clause G12 of the New
Zealand Building Code.
WATER HEATER APPLICATION
This water heater is designed for the purpose of heating potable water by
simultaneously reducing building chilling load. Its use in an application other than
this may shorten its life
If this water heater is to be used where an uninterrupted hot water supply is
necessary for the application or business, then there should be redundancy
within the hot water system design. This should ensure the continuity of hot water
supply in the event that this water heater was to become inoperable for any
reason. We recommend you provide advice to the system owner about their
needs and building backup redundancy into the hot water supply system.
COMPONENTS
The heat pump water heater system is modular and comprises three main
components: the heat pump water heater, storage tanks, and primary circulators.
An auxiliary booster and circulator may also be employed as part of the system.
The water heater must not be operated until all components are assembled.
Do not
tilt the heat pump more than 45° from the vertical
. This will unsettle
the refrigerant gas and compressor lubricating oil. If the heat pump has been
tilted more than 45° from the vertical during handling, it will need one hour to
settle before the power to the water heater can be switched on, otherwise
damage to the compressor may result.
INDOOR INSTALLATION
To comply with AS1677.2, the minimum room size permissible is 5.6m
3
per 15kW
heat pump and 15.34 m
3
per 35kW heat pump.
Summary of Contents for W2W Series
Page 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Page 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Page 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Page 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Page 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Page 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Page 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Page 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...