61
Commissioning Procedure- BMS Configuration
Before commencing the commissioning procedure, ensure the
installation procedure has been
completed as stated on
page 47
If the system is comprised of single or multiple standalone heat pumps,
perform this procedure for each heat pump. Each heat pump will have
its own BMS card.
If the system is comprised of multiple heat pumps for Master/Slave
operation, perform this procedure for only master heat pump. Only
master heat pump will have a BMS card and the slave heat pumps will
be connected via LAN cable.
Configure BMS settings from the display of the heat pump.
After commissioning the Master heat pump, go to the Service menu
(Service- password 0022>BMS config). Refer to
navigating Service menu.
BMS configuration (will time out after 5 minutes if no buttons pressed)
Address: 1 (Change address if required)
Protocol: CAREL
Speed: 19200
(Change the protocol as required if Modbus or BacNet is used)
Summary of Contents for W2W Series
Page 24: ...INSTALLATION 24 Typical Installation with Recirculation ...
Page 25: ...INSTALLATION 25 Typical Installation with Inline Auxiliary Boost ...
Page 26: ...INSTALLATION 26 Typical Installation with Rheem Guardian Warm Water System ...
Page 27: ...INSTALLATION 27 Dimensions and Technical Data RHEEM W2W Model 15kW 95401500 ...
Page 28: ...INSTALLATION 28 Dimensions and Technical Data RHEEM W2W Model 35kW 95403500 ...
Page 29: ...INSTALLATION 29 Dimensions and Technical Data RHEEM W2W Stackable Model 15kW 9540150S ...
Page 30: ...INSTALLATION 30 Dimensions and Technical Data RHEEM W2W Stackable Model 35kW 9540350S ...
Page 48: ...15KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 49: ...CONNECTIONS ELECTRICAL 49 35KW HEAT PUMP INTERNAL WIRING DIAGRAM ...
Page 50: ...CONNECTIONS ELECTRICAL 50 Controller and Display Information ...