Air
Refrigerant Line Size Information
RARL- JEZ Series
Suction Line Run
Feet [m]
25'
[7.62]
50'
[15.24]
100'
[30.48]
150'
[45.72]
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
5
/
8
" [15.88 mm] O.D. Std.*
3
/
4
" [19.05 mm] O.D. Opt.
—
1.00
1.00
—
0
.99
1.00
—
0
.97
0
.98
—
0
.95
0
.97
Suction Line Length/Size and Capacity Multiplier
2-Stage R-410A
System Capacity Model
2 Ton
3 Ton
5
/
8
" [15.88 mm] O.D. Opt.
3
/
4
" [19.05 mm] O.D. Std.*
.99
1.00
N/A
0
.98
0
.99
N/A
0
.95
0
.97
N/A
0
.91
0
.95
N/A
4 Ton
3
/
4
" [19.05 mm] O.D. Opt.
7
/
8
" [22.23 mm] O.D. Std.*
1.00
1.00
N/A
0
.98
0
.99
N/A
0
.95
0
.97
N/A
0
.93
0
.95
N/A
5 Ton
.99
1.00
N/A
0
.98
0
.99
N/A
0
.94
0
.97
N/A
0
.91
0
.95
N/A
Suction Line Connection Size
3/4" [19.05] I.D.
7/8" [22.23] I.D.
2-Stage
R-410A
System
Capacity
Model
Line Size
(Inch O.D.)
[mm]
Liquid Line Size
Outdoor unit above Indoor Coil (Cooling Only)
Liquid Line Size
Outdoor unit Below Indoor Coil (Cooling Only)
Minimum Vertical Separation—Feet [m]
Maximum Vertical Separation—Feet [m]
25
[7.62]
50
[15.24]
75
[22.86]
100
[30.48]
125
[38.10]
150
[45.72]
25
[7.62]
50
[15.24]
75
[22.86]
100
[30.48]
125
[38.10]
150
[45.72]
Total Equivalent Length—Feet [m]
Total Equivalent Length—Feet [m]
5/16 [7.94]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
40 [12.19]
35 [10.66] 29 [8.83] 22 [6.70]
2 Ton
1/4* [6.35]
0
0
17 [5.18]
43 [13.10] 70 [21.33]
95 [28.95]
25 [7.62]
10 [3.04]
N/A
N/A
N/A
N/A
5/16
″
[7.94]
Liquid Line
Connection
Size
(Inch I.D.)
3/8
[9.53]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
51 [15.54]
48 [14.63] 44 [13.41] 40 [12.19]
3 Ton
5/16* [7.94]
0
0
0
0
0
7
25 [7.62]
39 [11.88]
28 [8.53]
16 [4.87]
5 [1.52]
N/A
5/16
″
[7.94]
3/8
[9.53]
0
0
0
0
0
0
25 [7.62]
47 [14.32]
40 [12.19]
32 [9.75] 24 [7.31] 17 [5.18]
4 Ton
5/16* [7.94]
0
0
8 [2.43]
32 [9.75]
55 [16.76]
80 [24.38]
25 [7.62]
15 [4.57]
N/A
N/A
N/A
N/A
3/8
″
[9.53]
1/2
[12.7]
0
0
0
0
0
0
25 [7.62]
50 [15.24]
56 [17.06]
54 [16.45] 52 [15.84] 50 [15.24]
5 Ton
3/8* [9.53]
0
0
0
0
0
0
25 [7.62]
41 [12.49]
30 [9.14]
20 [6.09] 10 [3.04]
0
3/8
″
[9.53]
3/8
[9.53]
0
0
0
0
0
0
25 [7.62]
50 [15.24] 45 [13.71] 42 [12.80] 39 [11.88] 37 [11.28]
NOTES: N/A = Application not recommended.
*Standard line size
NOTES: Line size not recommended due to inadequate oil return.
*Standard line size
[ ] Designates Metric Conversions
Condensing Unit Refrigerant Line Size Information
31
Summary of Contents for Prestige RARL-JEZ Series
Page 33: ...Air Notes RARL JEZ Series 33...
Page 34: ...Air Notes RARL JEZ Series 34...
Page 35: ...Air Notes RARL JEZ Series 35...