29
Model
Number
RARL
ELECTRICAL
PHYSICAL
Phase
Frequency (Hz)
Voltage (Volts)
Compressor
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil
Refrig.
Per
Circuit
Oz. [g]
Weight
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
Rev. 5/8/2012
025JEZ 1-60-208/230
11.7/11.7
58.3
0.75
16/16
20/20
25/25
15.82 [1.47]
1
2285 [1078]
104 [2948]
197 [89.4]
210 [89.4]
038JEZ 1-60-208/230
15.3/15.3
83
1
21/21
25/25
35/35
23.01 [2.14]
1
3400 [1604]
186 [5273]
216 [98]
229 [98]
049JEZ 1-60-208/230
21.2/21.2
104
1
28/28
35/35
45/45
23.01 [2.14]
1
3400 [1604]
180 [5103]
252 [114.3]
265 [120.2]
061JEZ 1-60-208/230
28.8/28.8
152.9
2.8
39/39
50/50
60/60
23.01 [2.14]
2
3500 [1652]
243 [6889]
283 [128.4]
296 [128.4]
NOTE: Factory Refrigerant Charge includes refrigerant for 15 feet of standard line set.