4.5.6. Auxiliary source 0-10V
The heat source can be switched on or off by the user with the
ON/OFF
button.
Settings page intended for sources modulated by 0-10V voltage signal.
Measured temperature at the control
sensor and desired temperature for the
auxiliary heat source. Current output of the
source in percent.
Status of auxiliary heat source and
Ripple control (if used).
Limitation of the minimum and maximum boiler
outlet temperature. These values are set by the
technician in the service menu during
commissioning.