2.1. Heating
Zones
Heating Zone basic settings
T comfort (°C)
............ Setting comfort temperature in zone (desired room temperature).
T setback (°C)
............ Setting setback temperature in zone (desired room temperature).
During a day, the controller switches the desired zone temperatures by the preset time
schedule (for zones 3 to 6 adjustable from the web interface only).
zone on
....................... Switching on a heating zone on the User level. When a zone is
switched off on the User level, the circulation pump will be switched off
and the mixing valve will shift to closed position.
The pump and valve can be activated by frost protection (if on and active).
Summer/winter mode
state
............................ Switching on/off the function for automatic transition between summer
and winter modes.
Summer/Winter
mode is intended to turn on zone
heating when the outdoor temperature stays below the preset
threshold temperature
(winter temp)
for a certain time
(winter time)
,
and vice versa, to turn off zone heating when the outdoor temperature
exceeds the preset threshold temperature
(summer temp)
for a
certain time
(summer time)
.
summer temp (°C)
..... If the outdoor temperature keeps above this value for the time set in
parameter
summer time
, the Controller will switch to
summer
mode.
summer time (h)
........ see
summer temp.
winter temp (°C)
......... If the outdoor temperature keeps below this value for the time set in
parameter
winter time
, the Controller will switch to
winter
mode.
winter time (h)
............ see
winter temp.