12
2.2. HVAC
Unit
HVAC Zone basic settings
comfort (%)
................ HRV unit power settings during a "comfort“ mode from 15 to 100%.
setback (%)
................ HRV unit power settings during a "setback“ mode from 15 to 100%.
During a day, the controller switches the desired HVAC unit power by the preset time schedule
(adjustable from the web interface only).
zone on
....................... Switching on Zone on the User level.
Boost function 1, 2, 3 settings
boost 1, 2, 3
................ Switching on the Boost function. HVAC unit power will be temporarily
raised to the set
power
level for a time span set by the
period
value.
After the Boost period expires, the HVAC unit will be switched back to
automatic mode. This function could be also switched on by a button
connected to one of the controller inputs (see the service level).
power (%)
................... see
boost 1, 2, 3
.
duration (hh:mm)
....... see
boost 1, 2, 3
.
Summer bypass settings
Summer bypass
......... Switching on the Summer bypass function. This function can be
assigned to a room sensor in one of heating zones (however only when
a room sensor/unit is present in the respective zone). The installed
sensor is defined by the parameter
Summer bypass off assign
function to
. This function opens the bypass flap when the outside
temperature is lower than set temperature for the selected room sensor
(request t.)
. At the same time, the outdoor temperature has to be
higher than the minimum outdoor temperature
(min.out.t.)
set on the
service level. The summer bypass function can only be switched on in
the summer mode of the selected zone (can be set on the service
level).
assign function to zone (zone number 1 – 6)
.................................... see summer
bypass
.
request t. (°C)
............. see summer
bypass
.