Default = Auto
Communication speed on the Ethernet interface.
Modbus TCP*
Use this setttings only for
Modbus TCP Master
when it communicates with both types of Modbus
slaves using either Modbus RTU or Modbus TCP protocols. Or when TCP/IP communication should
run locally between Modbus Master and RipEX in Modbus TCP network. Read Help and Application
note Modbus in RipEX.
For more information refer to the manual Application note / Modbus TCP
1
.
** - denotes items to be used only when either all or some RTUs (Remote Telemetry Unit) on remote
sites are connected via RS232 or RS485 interface to RipEX, using the Modus RTU protocol. Then
automatic conversion between Modbus TCP and Modbus RTU protocols takes place for such units.
List box: On, Off
Default = Off
•
My TCP port
Default = 502 [1 - 65 535]
TCP port used for Modbus TCP in RipEX.
•
TCP Keepalive [sec.]
Default = 120 [0 - 16 380]
TCP socket in RipEX is kept active after the receipt of data for the set number of seconds.
•
Broadcast**
List box: On, Off
Default = Off
Some Master SCADA units send broadcast messages to all Slave units. SCADA application typically
uses a specific address for such messages. RipEX (Protocol utility) converts such message to an
IP broadcast and broadcasts it to all RipEX units resp. to all SCADA units within the network.
If On, the address for broadcast packets in SCADA protocol has to be defined:
•
Broadcast address format
- List box Hex, Dec - format in which broadcast address is defined.
•
Broadcast address
- address in the defined format (Hex, Dec)
•
Address translation
List box: Table, Mask
Default = Mask
In a SCADA protocol, each SCADA unit has a unique address, a "Protocol address". In RipEX Radio
network, each SCADA unit is represented by an IP address (typically that of ETH interface) and a
UDP port (that of the protocol daemon or the COM port server to which the SCADA device is con-
nected via serial interface).
A translation between "Protocol address" and the IP address & UDP port pair has to be done. It
can be done either via Table or via Mask.
Each SCADA message received from serial interface is encapsulated into a UDP/IP datagram,
where destination IP address and destination UDP port are defined according the settings of Address
translation.
○
Mask
Translation using Mask is simpler to set, however it has some limitations:
− all IP addresses used have to be within the same network, which is defined by this Mask
1
http://www.racom.eu/eng/products/m/ripex/app/modbus.html
79
© RACOM s.r.o. – RipEX Radio modem & Router
Advanced Configuration