26
WIRING INSTRUCTIONS FOR TEMPLATE 3:
1)
Turn RTU on, and Disarm it (so that the right hand Arm/Disarm LED blinks).
2)
Designate (identify) a Pump 1, Pump 2 and Pump 3 for the purposes of AlarmAgent
monitoring.
3)
Verify that all contact inputs are dry (non-powered). Otherwise, RTU will be damaged.
4)
Connect contact inputs for Pump 1, Pump 2 and Pump 3.
5)
Connect any other desired inputs to channels 4 through 10 See separate instructions
and diagram for using Channels 9 and 10 as analog inputs.
6)
Place any contact inputs to Channels 4 through 10 in their normal, non-alarm state.
Press the ACCEPT pushbutton. This automatically configures Channels 4 through 10 to
alarm on the opposite input state.
7)
TEST WIRING! Verify the following:
a)
Channel 1 LED activates when Pump 1 runs.
b)
Channel 2 LED activates when Pump 2 runs.
c)
Channel 3 LED activates when Pump 3 runs.
Test wiring for any remaining inputs by manipulating their state and verifying that the corresponding
Channel LED activates when the input is closed (and deactivates when the input is open).