NOTES:
Dry (non-powered) contact inputs only!
Channels 1, 2 and 3 may be independently configured for pulse totalizing, run time
accumulation or simple digital inputs via the web site.
To use Channels 9 or 10 as analog inputs, see separate diagram.
Ground connection is important for surge protection.
Terminals accommodate #16 to #26 wire size.
WIRING INSTRUCTIONS FOR TEMPLATE 5:
1)
Turn RTU on, and Disarm it (so that the right hand Arm/Disarm LED blinks).
2)
Connect input wiring as needed per the above diagram.
3)
Place all inputs in their normal, non-alarm state. Press the ACCEPT pushbutton. This
automatically configures inputs to alarm on the opposite input state.
4)
If any inputs (such as run time or totalizer inputs) are to be non-alarming, after using the
Accept pushbutton, configure those inputs as Status Only via the web site.