Section IX – Technical data
110 Quincy Vacuum Pump-QSV Series
Installation method F according table B.52.1. Single-core
cables, touching in free air Clearance to wall not less than one
cable diameter
Maximum allowed current in function of the ambient temperature for installation method F
Calculation method for IEC:
Single supply cables (3 PE - configuration (1)):
Add 10% to the total vacuum pump current (Itot from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 PE - configuration (2)):
Add 10% to the total vacuum pump current (Itot from the tables) and divide by 2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 PE as in (3):
Add 10% to the total vacuum pump current (Itot from the tables) and divide by
√3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Fuse size: the recommended maximum fuse size divided by
√
3 on each cable.
Size of the PE cable:
For supply cables up to 35 mm²: same size as supply cables
For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5% of the nominal voltage is recommended).
Example: Itot= 89 A, maximum ambient temperature is 45 °C, recommended fuse = 100 A
Single supply cables (3 PE - configuration (1)):
I = 89 A + 10% = 89 x 1.1 = 97.9 A
The table for B2 and ambient temperature = 45 ° C allows a maximum current of 93 A for a 50 mm²
cable. For a cable of 70 mm², the maximum allowed current is 118 A, which is sufficient. Therefore,
use a 3 x 70 mm² + 35 mm² cable. If method C is used, 50 mm² is sufficient. (35 mm² for method F)
=>cable 3 x 50 mm² + 25 mm².
Parallel supply cable (2 x 3 PE - configuration (2)):
I = (89 A + 10%)/2 = (89 x 1.1)/2 = 49 A
Summary of Contents for QSV 2200
Page 1: ...Quincy Oil sealed rotary screw vacuum pumps QSV 2200 QSV 2700 QSV 3200 Instruction Manual...
Page 2: ......
Page 4: ...This page intentionally left blank...
Page 14: ...Section II General description 14 Quincy Vacuum Pump QSV Series Open view front Open view back...
Page 61: ...Section IV Installation Quincy Vacuum Pump QSV Series 61 Installation 4 1 Dimension drawings...
Page 62: ...Section IV Installation 62 Quincy Vacuum Pump QSV Series 4 2 Installation proposal...
Page 122: ...Notes 122 Quincy Vacuum Pump QSV Series...
Page 123: ......
Page 124: ...www quincycompressor com No 6996 0227 39 2017 09 Printed in USA...