25
E
N
G
L
I
S
H
Partially open function
It activates with parameter F=0 of operation selected by user, the percentage of opening of the door
is selected using the parameter H 1=5% 2=10% 3=20% 4=30% 5=40% 6=50% 7=60% 8=80%
If you insert parameter M=1, dynamic partial opening is activated. If the door fails to close three
time consecutively, upon expiration of the automatic closing time, the door will be completely
opened.
Operation of the electronic clutch
This device is very important in terms of safety. Its calibration is self-learning. Impact force can be
changed with the parameter at 1=maximum sensitivity 2=medium-maximum sensitivity 3=medium-
minimum sensitivity 4=minimum sensitivity
A.
It is active during both opening and closing. If it intervenes during closing it reverses the
direction of movement without disabling automatic closing. During opening, it reverses the
direction of movement for 1 second and then closes again at the automatic closure time,
travelling the entire distance in slow motion
B.
If it intervenes three consecutive times, it automatically goes to STOP and disables
automatic closure. This emergency can be exited via an OPEN KEY, EXT. RADAR, or
INT. RADAR impulse. It will always carry out a slow-motion opening. This will be
followed by a realignment cycle shown by the message
RS.
The operating status selected by
the user will then be activated
Operation with backup battery
This function is contingent upon selection of parameter N
N=0 Operation without backup battery. Excludes any automatic manoeuvre and control of the
battery charger
N=1 If there is a power outage, it performs a single door opening. The door is kept open and
automatic closure is blocked. When the power comes back on, the automatic closing time is
reloaded.
N=2 If there is a power outage, a single door closing is carried out and the door is kept closed. This
condition can be exited only when the power comes back on and with an OPEN KEY impulse
(operation as firewall door)
N.B. No manoeuvre is performed if the selected operating status is night
(NI)
Resetting the control unit
This condition occurs at first start-up, when there is a power outage with no backup batteries or with
dead batteries, at each STOP activation, and each time the electronic clutch is activated. The door
carries out the first opening and closing in slow-motion, with the display showing
RS
Summary of Contents for WINNY LIGHT
Page 5: ...5 E N G L I S H 4 SPACE REQUIRED VERTICAL SECTION ...
Page 6: ...6 VERTICAL SECTION WITH CRASH BAR ...
Page 27: ...27 E N G L I S H ...
Page 28: ......
Page 33: ...5 I T A L I A N O 4 SPAZI RICHIESTI ...
Page 34: ...6 ...
Page 35: ...7 I T A L I A N O ...
Page 55: ...27 I T A L I A N O ...