SIE Protocol
PLX3x Series ♦ Multi-Protocol Gateways
User Manual
Page 172 of 215
ProSoft Technology, Inc.
January 25, 2018
9.3.3 SIE Error Codes
SIE Module Communication Error Codes
Decimal Hex
Description
1
0x0001
No data from I/O module
3
0x0003
The desired item is not available in the PLC (200 family)
5
0x0005
The desired address is beyond limit for this PLC
6
0x0006
The CPU does not support reading a bit block of length<>1
7
0x0007
Write data size error
10
0x000a
The desired item is not available in the PLC
-123
0xff85
Cannot evaluate the received PDU
-124
0xff84
The PLC returned a packet with no result data
-125
0xff83
The PLC returned an error code not understood by this library
-126
0xff82
This result contains no data
-127
0xff81
Cannot work with an undefined result set
-128
0xff80
Unexpected function code in answer
-129
0xff7f
PLC responds with an unknown data type
-1024
0xfc00
Short packet from PLC
-1025
0xfbff
Timeout when waiting for PLC response
-32767
0x8001
Not allowed in current operating status
-32511
0x8101
Hardware fault
-32509
0x8103
Object access not allowed
-32508
0x8104
Context is not supported. Step7 says: Function not implemented or error in
telegram
-32507
0x8105
Invalid address
-32506
0x8106
Data type not supported
-32505
0x8107
Data type not consistent
-32502
0x810A
Object does not exist
-31999
0x8301
Insufficient CPU memory
-31742
0x8402
CPU already in RUN or already in STOP
-31740
0x8404
Severe error
-31488
0x8500
Incorrect PDU size
-30974
0x8702
Address invalid
-12286
0xd002
Step7: Variant of command is illegal
-12284
0xd004
Step7: Status for this command is illegal
-12127
0xd0A1
Step7: Function is not allowed in the current protection level
-11775
0xd201
Block name syntax error
-11774
0xd202
Syntax error function parameter
-11773
0xd203
Syntax error block type
-11772
0xd204
No linked block in storage medium
-11771
0xd205
Object already exists