Note: If you want to access module status data in the upper memory, you can use the data
mapping feature in the gateway to copy data from the module status data area to the user data
area. See Mapping Data in Module Memory (page 24). Otherwise, you can use the diagnostic
functions in ProSoft Configuration Builder to view module status data. For more information on the
module status data, see PND Diagnostics (page 205).
10.2 PND Configuration
The following procedure shows how to configure a PLX3x gatewayGateway with
the PND protocol using ProSoft Configuration Builder (PCB). This configuration
provides the ability to communicate with a Siemens processor via the PROFINET
protocol. This example uses a PLX31-EIP-PND gateway.
1
Launch ProSoft Configuration Builder.
2
Create a new PLX31-EIP-PND module.
3
Click
OK
.