Using ProSoft Configuration Builder
PLX3x Series ♦ Multi-Protocol Gateways
User Manual
Page 24 of 215
ProSoft Technology, Inc.
January 25, 2018
2
Click any parameter in the
Edit - WATTCP
dialog box to change the value. If
your gateway has two Ethernet ports (PLX32) there are separate
configuration options for each port.
Parameter
Description
IP Address
Unique IP address assigned to the module
Netmask
Subnet mask of module
Gateway
Gateway (if used)
Note: Each Ethernet port must be on a different Ethernet subnet.
To determine the protocol for an Ethernet port in PCB (PLX32 only)
1
In
ProSoft Configuration Builder
, click the
[+]
next to the gateway, then click
the
[+]
next to
Module
.
2
Double-click the second
Module
icon.
3
In the
Edit - Module
dialog box, click the port to see the protocol for that port.
You cannot change the protocol assigned to a port.
2.7
Mapping Data in Module Memory
Use the
DATA MAP
section in the ProSoft Configuration Builder to copy data
between areas in the gateway's internal database. This allows you to copy data
to different addresses within the gateway database in order to create simpler
data requests and control. You can use this feature for the following tasks.
Copy a maximum of 100 registers per Data Map command, and you can
configure a maximum of 200 separate copy commands.
Copy data from the error or status tables in upper memory to internal
database registers in the
user data area.
Rearrange the byte and/or word order during the copy process. For example,
by rearranging byte or word order, you can convert floating-point values to
the correct format for a different protocol.
Use the Data Map to condense widely dispersed data into one contiguous
data block, making it easier to access.