PLX3x Series ♦ Multi-Protocol Gateways
EIP Protocol
User Manual
ProSoft Technology, Inc.
Page 79 of 215
January 25, 2018
5
Fill in the
M
ULTI
H
OP
tab portion of the dialog box as shown in the following
image.
6
Set the
T
O
A
DDRESS
value to the gateway’s Ethernet IP address.
7
Press the
INS
key to add the second line for ControlLogix Backplane and set
the slot number to zero.
SLC File Types
This information is specific to the SLC and MicroLogix family or processors used
with the PCCC command set. The SLC and MicroLogix processor commands
support a file type field entered as a single character to denote the data table to
use in the command. The following table defines the relationship of the file types
accepted by the gateway and the SLC file types.
File Type
Description
S
Status
B
Bit
T
Timer
C
Counter
R
Control
N
Integer
F
Floating-point
Z
String
A
ASCII
The
File Type Command Code
is the ASCII character code value of the File Type
letter. This is the value to enter for the
F
ILE
T
YPE
parameter of the PCCC
Command configurations in the data tables in the ladder logic.
Additionally, the SLC specific functions (502, 510 and 511) support a sub-
element field. This field selects a sub-element field in a complex data table. For
example, to obtain the current accumulated value for a counter or timer, set the
sub-element field to 2.