Trimax Operation
Navigation: Home Screen>Main Menu>EZ Setup>DHW EZ Setup
Domestic Hot Water EZ Setup allows the installer to quickly customize the
domestic hot water settings for the application.
Select DHW Demand
Default: Sensor
Select DHW Demand prompts the installer to select the type of device which
will generate a DHW call. Press the
UP
or
DOWN
buttons to select the
DHW Demand type then press the
OK
button to store the setting. The Select
DHW Demand options are:
•
Switch
– A domestic hot water call from an aquastat or dry contact
switch will enable the Prestige with a fixed setpoint for a domestic hot
water call.
•
Sensor
– The Prestige Excellence utilizes an Indirect Water Heater
Sensor. The Prestige will monitor the DHW storage temperature and
generate a domestic hot water call when the temperature drops below
the DHW Storage Setpoint by 6ºF [3ºC].
DHW Storage Setpoint
Default: 140°F [60°C]
DHW Storage Setpoint prompts the installer to enter the domestic hot water
storage setpoint temperature when the Sensor option is chosen in Select
DHW Demand. Press the
LEFT
or
RIGHT
buttons to adjust the DHW
Storage Setpoint then press the
OK
button to store the setting.
The Boiler DHW Setpoint will automatically be set 46°F [25°C]
higher than the DHW Storage Setpoint setting.
DHW Priority Timeout
Default: Off
DHW Priority Timeout prompts the installer to enter an optional time limit
that a domestic hot water call has priority over a central heating call. Press
the
LEFT
or
RIGHT
buttons to adjust the DHW Priority Timeout then press
the
OK
button to store the setting.
NOTICE
Domestic Hot Water EZ Setup
Select DHW Demand
Switch
Sensor
Sensor
68ºF
150ºF
140ºF
DHW
Storage Setpoint
Off
120 min.
Off
DHW Priority Timeout