44
Trimax Operation
Select CH1 Reset Curve
Default: Finned Tube Baseboard
Select CH1 Reset Curve prompts the installer to select an outdoor reset curve
for a CH1 heating call when an Outdoor Reset option is chosen in Select CH
Demand. Outdoor reset curve presets are available to cover most applica-
tions. The outdoor reset curve can also be adjusted to any desired settings in
the Installer Menu. Press the
UP
or
DOWN
buttons to select the outdoor
reset curve appropriate for the type of heating system then press the
OK
but-
ton to store the setting.
Select CH2 Reset Curve
Default: Low Mass Radiant
Select CH2 Reset Curve prompts the installer to select an outdoor reset curve
for a CH2 heating call when an Outdoor Reset option is chosen in Select CH
Demand. Outdoor reset curve presets are available to cover most applica-
tions. The outdoor reset curve can also be adjusted to any desired settings in
the Installer Menu. Press the
UP
or
DOWN
buttons to select the outdoor
reset curve appropriate for the type of heating system then press the
OK
but-
ton to store the setting.
Set Warm Weather Shutdown Temperature
Default: OFF
Warm Weather Shutdown prompts the installer to enter an optional outdoor
temperature at which to disable the central heating function and any circu-
lators placed into constant circulation with the pump constant circulation
setting. The Prestige will continue to respond to a domestic hot water call
or a 0-10V Modulation Signal when the outdoor temperature exceeds the
Warm Weather Shutdown Temperature setting. Press the
LEFT
or
RIGHT
buttons to adjust the Warm Weather Shutdown Temperature then
press the
OK
button to store the setting. The Warm Weather Shutdown
icon
is displayed on the home screen when the outdoor temperature
reaches the Warm Weather Shutdown Temperature.
180ºF
120ºF
64ºF
0ºF
Current Settings
Table 3: Outdoor Reset Preset Selections
Preset
Minimum Setpoint
Maximum Setpoint
Low Mass Radiant
80ºF [27ºC]
140ºF [60ºC]
High Mass Radiant
80ºF [27ºC]
120ºF [49ºC]
Cast Iron Baseboard
100ºF [38ºC]
170ºF [77ºC]
Finned Tube Baseboard
120ºF [49ºC]
180ºF [82ºC]
Radiators
120ºF [49ºC]
170ºF [77ºC]
Fan Coil
140ºF [60ºC]
180ºF [82ºC]
Off
78ºF
Off
Warm Weather Shutdown