Chapter 5 Function parameter
37
Ch
ap
ter 5
112 F1.41 Keyboard Encoder X1
0
~
100.00%
0.00%
☆
113 F1.42 Keyboard Encoder X2
0
~
100.00%
0.50%
☆
114 F1.43 Keyboard Encoder set value
0
~
100.00%
-
☆
115 F1.44
Keyboard Encoder X1
corresponding value Y1
-100.00%
~
+100.00%
0.00%
☆
116 F1.45
Keyboard Encoder X2
corresponding valueY2
-100.00%
~
+100.00%
100.00%
☆
117 F1.46
Keyboard Encoder
control
Bits:
0: Power down protection
1: Power down zero clear
Ten bits:
0: Stop keep
1: Stop order zero clear
2: Stop over zero clear
Hundred bits: reserve
Thousand bits: reserve
00
☆
5-1-4.F2 Group - Output terminals group
No. Code
Parameter name
Setting range
Factory
setting
Chan-
ge
118 F2.00 SPB terminal output mode selection 0 to 1
0
☆
119 F2.01
Switching quantity output function
selection
0 to 40
0
☆
120 F2.02
Relay 1 output function selection
(TA1.TB1.TC1)
2
☆
121 F2.03 Undefined
122 F2.04
SPA output function selection
(collector open circuit output
terminals)
1
☆
123 F2.05
Relay 2 output function selection
(TA2.TB2.TC2)
1
☆
Above 5 function code is used to select five digital output function. Multifunctional output
terminal functions are as follows:
Setting
value
Functions
Description
0
No output
No output action
1
Inverter running
Inverter is in running state, the output frequency (can be
zero), the output ON signal.
2
Fault output (fault
down )
When the drive fails and downtime, the output ON signal.
3
Frequency level
detection FDT1 output
Please refer to the function code F7.23, F7.24's
instructions.
4
Frequency arrival
Please refer to the description of function code F7.25.
5
Zero-speed running (no
output when shutdown)
Inverter operation and the output frequency is 0, output
ON signal. When the drive is shut down, the signal is
OFF.