Chapter 5 Function parameter
31
Ch
ap
ter 5
10: analog quantity AI3 setting
47 F0.04
Frequency source
auxiliary setting
The same as F0.03
0
★
48 F0.05
Reference object
selection for frequency
source auxiliary setting
0. relative to maximum frequency
1.relative to master frequency source 1
2. relative to master frequency source 2
0
☆
49 F0.06
Frequency source
auxiliary setting range
0% to 150%
100%
☆
50 F0.07
Frequency source
superimposed selection
Units digit: frequency source selection
Tens digit: arithmetic relationship of
master and auxiliary for frequency
source
00
☆
51 F0.08
Frequency source offset
frequency when
superimposing
0.00Hz to F0.19(maximum frequency)
0.00Hz
☆
52 F0.09
Shutdown memory
selection for digital set
frequency
0: W/O memory
1: With memory
1
☆
53 F0.10
Frequency command UP
/ DOWN reference when
running
0: Running frequency
1: Set frequency
0
★
54 F0.11
Command source
selection
0.Keyboard control (LED off)
1.Terminal block control (LED on)
2.Communications command control
(LED flashes)
3. Keyboard Communications
command control
4. Keyboard Communications
command Terminal block
control
0
☆
55 F0.12
Binding frequency
source for command
source
Units digit: binding frequency source
selection for operation panel command
0: no binding;
1. Keyboard setting frequency;
2: analog quantity AI1 setting
3: analog quantity AI2 setting
4: panel encoder setting
5: high speed pulse setting
6: multi-speed setting
7: simple PLC setting
8: PID setting
9: communication given
Tens digit: terminal command binding
frequency source selection (0 to 9, same
as units digit)
Hundreds digit: communication
command binding frequency source
selection (0 to 9, same as units digit)
000
☆
56 F0.13 Acceleration time 1
0.00s to 6500s
Depends
on models
☆