Chapter 5 Function parameter
39
Ch
ap
ter 5
27
Frequency 2 reaches
output
Please refer to the function code F7.30, F7.31's
instructions.
28
Current 1 reaches output
Please refer to the function code F7.36, F7.37's
instructions.
29
Current 2 reaches output
Please refer to the function code F7.38, F7.39's
instructions.
30
Timing reach output
When the timer function selection (F7.42) is valid, the
drive time to reach this run after the set time runs out,
output ON signal.
31
AI1 input overrun
When the value of analog input AI1 greater than F7.51
(AI1 input protection limit) or less than F7.50 (AI1 input
protection under), output ON signal.
32
Off load
When the inverter is off-load state, output ON signal.
33
Reverse operation
Inverter in reverse run, output ON signal
34
0 current state
Refer to the description of function code F7.32, F7.33.
35
Module temperature
reaches
Inverter module heatsink temperature (F6.06) reach the
set module temperature reaches value (F7.40), output
signal ON.
36
Software current limit
Please refer to the function code F7.34, F7.35's
instructions.
37
The lower frequency
arrival (stop and output)
When the operating frequency reaches the lower limit
frequency, output ON signal. In shutdown state of the
signal is also ON.
38
Alarm output
When the inverter failure, and the failure of the process to
continue to run mode, the inverter alarm output.
39
Motor overtemperature
pre-warning
When the motor temperature reaches F8.35 (motor
overheat pre-alarm threshold), the output ON signal.
(Motor temperature can be viewed at d0.41)
40
Current running time of
arrival
When the inverter starts running time is longer than the
time set by F7.45, it outputs ON signal.
124 F2.06
High-speed pulse output function
selection
0 to 17
0
☆
125 F2.07 DA1 output function selection
2
☆
126 F2.08 DA2 output function selection
13
☆
High-speed pulse output frequency range of 0.01kHz ~ F2.09 (high speed pulse output
maximum frequency), F2.09 can be set between 0.01kHz ~ 100.00kHz.
Analog Output DA1 and DA2 output range is 0V ~ 10V, or 0mA ~ 20mA. Pulse output or
analog output range, with the corresponding scaling function relationship in the following table
:
Setting
value
Functions
Description
0
Running frequency
0~Max. output frequency
1
Set frequency
0~ Max. output frequency
2
Output current
0~2 times the motor rated current
3
Output torque
0~2 times the motor rated toqure
4
Output power
0~2 times rated power
5
Output voltage
0~1.2 times inverter rated voltage
6
High speed pulse input
0.01kHz~100.00kHz