Chapter 4 Installation and commissioning
24
Ch
ap
ter 4
Category
Symbol
Name
Function
Motor
temperature
inspection
input
S1-
S2-
GND
PT100 inspect
wire input
PT100 temperature senso.
Note: such as PT100 three
detection line, with a universal table test, to find two of
the detection line is 0Ω after the one received S2
terminal, the other received a GND; the remaining one
received S1 terminal.
Built-in
RS485
485+
485 differential
terminal
485 communication interface, 485 differential signal
terminal, use twisted-pair or shielded wire connect to the
standard 485 communication interface
485 jump line in the control panel to decide whether to
connect the terminal resistance
485-
485 differential
signal - terminal
Auxiliary
interface
J13
communication
interface
CAN card, 26-pin terminal
J10
PG card interface 12-pin terminal
GND
GND ground
interface
GND jump line decide whether to connect PE, improve
the inverter anti-interference
COM
COM ground
interface
COM jump line decide whether to connect PE, improve
the inverter anti-interference
H1
COM Terminal
interface
Consistent with the COM function on the terminal line
。
Signal input terminal circuit
Switch input and output signal transmission, generally use the shielded cable and wiring short
distance as far as possible, good grounding and shielding layer on the inverter side, try not to over 20
m transmission distance. Drive in active way, elected to the power of crosstalk necessary filtering
measures are taken, generally recommend that choose dry contact control mode.
Wiring control cable should be kept with the main circuit and high voltage lines (such as the
power cord, motor connecting line, relay or contactor) more than 20 cm distance, and to avoid high
voltage lines parallel to and can't be avoided and the high voltage lines cross, the proposal USES
vertical wiring way, in order to prevent the misoperation caused by disturbance frequency converter
Dry contact mode:
+24V
COM
PLC
(Default)
DI1
DI8
COM
PLC
PE
Shielded
cable
External
contactor
Inverter
Inner power supply with main connect
+24V
COM
PLC
(Default)
DI1
DI8
COM
PLC
PE
Shielded
cable
External
contactor
Inverter
External power supply with main connection
External power
supply
+
-
Figure 4-16
:
Signal input terminal circuit- dry contact mode
Note: using an external power supply, PLC and 24 v jumper cap must be removed, otherwise it
will damage the product.
Open collector NPN connect wire:
When the input signal from the NPN transistor, according to the use of power supply, please
according to the 24 v and PLC jumper cap.