The voltage drop depends on the cable length and the conductor's
cross section.
The following table shows some cable examples. The values are typ-
ical and only offered as guidelines.
n
For proper compensation, calculate the actual values as shown in
the following section.
Conductor
cross section
[mm
2
]/[AWG]
Specific
resistance
[
Ω
/m]
Cable length
[m]
Voltage drop
at 100 mA [V]
0.08 / AWG 28
0.235
10
0.47
20
0.94
35
1.65
0.14 / AWG 25
0.131
10
0.26
20
0.52
35
0.92
0.25 / AWG 23
0.075
10
0.15
20
0.30
35
0.53
0.5 / AWG 20
0.040
10
0.08
20
0.16
35
0.28
0.75 / AWG 18
0.025
10
0.05
20
0.10
35
0.18
Examples
PA 8000 LW CNC control unit
Installation
25.09.2015 | 99