4.16.2
Transferring a safety-related project to the safety-related
controller (defining a controller password, if necessary)
To transfer the project to the safety-related controller, proceed as follows:
•
Double-click on the “Safety PLC (x)” node in the “PLANT” area.
The “Safety PLC” editor group opens.
•
Select the “Safety Cockpit” editor.
•
Click on the
button.
Defining a controller
password for the safety-
related controller
The safety-related controller is protected by a controller password. Writing data to the
safety-related PLC or changing its operating mode is only possible after entering the con-
troller password in PLCnext Engineer.
If this is the first time you are attempting to connect to the safety-related controller,
PLCnext Engineer will prompt you to define a controller password.
•
Specify a controller password, if you have not already done so, and the following dialog
will be displayed.
Figure 4-57
Controller password: entering the password for the safety-related controller
User authentication
If necessary, refer to the information about user authentication on
•
If necessary, enter the user name and password in the dialog that opens.
Please note: read information dialogs carefully and follow the instructions pro-
vided
If information dialogs appear, please refer to the online help for PLCnext Engineer for fur-
ther information.
•
Acknowledge the messages in accordance with your application.
In the example:
Make sure no hazard is posed by the safety-related controller being started and/or
stopped, e.g., after downloading a project.
Ensure the safety function is in order.
Summary of Contents for RFC 4072S
Page 22: ...RFC 4072S 22 272 PHOENIX CONTACT 108580_en_02...
Page 68: ...RFC 4072S 68 272 PHOENIX CONTACT 108580_en_02...
Page 82: ...RFC 4072S 82 272 PHOENIX CONTACT 108580_en_02...
Page 142: ...RFC 4072S 142 272 PHOENIX CONTACT 108580_en_02...
Page 154: ...RFC 4072S 154 272 PHOENIX CONTACT 108580_en_02...
Page 222: ...RFC 4072S 222 272 PHOENIX CONTACT 108580_en_02...
Page 234: ...RFC 4072S 234 272 PHOENIX CONTACT 108580_en_02...
Page 254: ...RFC 4072S 254 272 PHOENIX CONTACT 108580_en_02...
Page 264: ...RFC 4072S 264 272 PHOENIX CONTACT 108580_en_02...
Page 268: ...RFC 4072S 268 272 PHOENIX CONTACT 108580_en_02...
Page 271: ......