F_Destination_Address
(F_Dest_Add)
•
Under the “Profinet (x)” node in the “PLANT” area, double-click on the lower-level node
of the safety module whose F-Address you want to set.
The safety module editor group opens.
•
Select the “Safety Parameters” editor.
Figure 4-42
F-Address of the PROFIsafe F-Device: F_Dest_Add (F_Destination_Ad-
dress)
•
In the “F_Parameter” view, check the setting for the F_Dest_Add F-Address.
•
Set F_Dest_Add to the value that corresponds to the DIP switch setting of the safety
module.
•
Set F_Dest_Add to “1” for the AXL F PSDI8/4 1F safety module in the example.
•
If necessary, adapt the value of F_Dest_Add to your application.
An adjustable range of “1 … 65535
dec
”, maximum, is permitted.
•
Set F_Dest_Add to “2” for the AXL F PSDO8/3 1F safety module in the example.
•
Proceed as described for other safety modules in your application.
When using the RFC 4072S as an F-Host, an adjustable range of “1 … 65534
dec
”, maxi-
mum, is permitted for the F-Addresses of the safety modules used (F_Dest_Add / F_Des-
tination_Address). Please note the following points:
–
Only assign F_Dest_Add values once.
–
For safety modules from Phoenix Contact, you can set PROFIsafe destination
addresses from 1 to 999
dec
, maximum.
–
For safety modules from other manufacturers, you can set PROFIsafe destination
addresses from 1 to 65534
dec
.
If you are not currently logged into the safety-related area, you will now be prompted to
enter the password in the “PROJECT AUTHENTICATION” dialog that opens (see
).
Summary of Contents for RFC 4072S
Page 22: ...RFC 4072S 22 272 PHOENIX CONTACT 108580_en_02...
Page 68: ...RFC 4072S 68 272 PHOENIX CONTACT 108580_en_02...
Page 82: ...RFC 4072S 82 272 PHOENIX CONTACT 108580_en_02...
Page 142: ...RFC 4072S 142 272 PHOENIX CONTACT 108580_en_02...
Page 154: ...RFC 4072S 154 272 PHOENIX CONTACT 108580_en_02...
Page 222: ...RFC 4072S 222 272 PHOENIX CONTACT 108580_en_02...
Page 234: ...RFC 4072S 234 272 PHOENIX CONTACT 108580_en_02...
Page 254: ...RFC 4072S 254 272 PHOENIX CONTACT 108580_en_02...
Page 264: ...RFC 4072S 264 272 PHOENIX CONTACT 108580_en_02...
Page 268: ...RFC 4072S 268 272 PHOENIX CONTACT 108580_en_02...
Page 271: ......