Nanoline
24
PHOENIX CONTACT
2338_en_O
1.
Clear any components around the desired mounting location on the enclosure.
2.
Using an appropriate tool for the enclosure material, cut a 119 x 93 ±0.5 mm hole in the
enclosure. Remove any burrs or sharp edges using a file or appropriate tool.
3.
Place the four J-hooks in the slots on the sides of the Operator Panel. Alternating
between the J-hooks, turn the screws in the J-hooks clockwise until they tighten against
the enclosure. Torque each J-hook screw to 0.5 - 0.6 Nm.
Figure 2-17
Remote Operator Panel installation
2.4
Connecting power, inputs and outputs
The Nanoline system components use a screw connection technology for power and I/O
connection. Individual connection points are labeled on the housing surface with
appropriate identifiers. Use a small screwdriver to turn the screw counterclockwise to
release and clockwise to tighten wires after insertion into the appropriate position.
NOTE:
Do not make the hole in the enclosure too large or the Operator Panel will pass through.
Do not drill holes for the mounting screws; they do not pass through the enclosure wall.
Operator
Panel
J-hook
Slot
Enclosure
panel
CAUTION:
Do not apply power to the Nanoline controller until directed to do so in the commissioning
(startup) procedure.
Summary of Contents for Nanoline NLC-035-024D-04I-02QRD-05A
Page 1: ...User manual Installing and using Nanoline controllers UM EN NLC...
Page 8: ...Nanoline 4 PHOENIX CONTACT 2338_en_O...
Page 38: ...Nanoline 34 PHOENIX CONTACT 2338_en_O...
Page 54: ...Nanoline 50 PHOENIX CONTACT 2338_en_O...
Page 66: ...Nanoline 62 PHOENIX CONTACT 2338_en_O...
Page 94: ...Nanoline 90 PHOENIX CONTACT 2338_en_O...