Mounting, removal, and electrical installation
7619_en_05
PHOENIX CONTACT
4.2
Electrical installation
4.2.1
Electrical installation of the Inline station
Electrical installation of the Inline station includes the following:
–
Connecting INTERBUS, PROFIBUS or PROFINET to the Inline station
–
Connecting the supply voltages for the Inline station
Carry out electrical installation for the Inline station according to the IL SYS INST UM E user
manual or the Inline system manual for your bus system. Please also observe the specifica-
tions in the documentation for the bus coupler used.
4.2.2
Electrical installation of the safety module
The supply voltages are supplied at a bus coupler and/or a power terminal and are supplied
to the safety module via the potential jumpers. Therefore, the electrical installation of the
safety module only involves connecting the actuators.
The actuators are connected via Inline plugs.
•
Wire the plugs according to your application. For the terminal point assignment, please
refer to Section “Terminal point assignment” on page 35.
For wiring, proceed as follows:
•
Strip 8 mm off the cable.
•
Push a screwdriver into the actuation shaft of the appropriate terminal point (Figure 4-6,
detail 1), so that you can insert the conductor into the spring opening.
Phoenix Contact recommends using a SZF 1 - 0.6X3.5 screwdriver (Order No.
1204517; see Phoenix Contact "CLIPLINE” part catalog).
•
Insert the conductor (Figure 4-6, detail 2). Remove the screwdriver from the opening.
This clamps the conductor.
WARNING: Electric shock / Unintentional machine startup
Prior to electrical installation, disconnect the power to the system and make sure that it
cannot be switched on again unintentionally.
Make sure installation has been completed before switching the power back on.
The system may only be started provided the system does not pose a hazard.
During installation, always observe the instructions in “Electrical safety” on page 10.
Take measures to prevent the mismatching, polarity reversal, and manipulation of con-
nections.
Inline wiring is normally carried out without ferrules. However, it is possible to use ferrules.
If using ferrules, make sure they are properly crimped.
Summary of Contents for IB IL 24 PSDO 8-PAC
Page 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Page 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Page 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Page 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Page 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Page 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Page 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Page 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Page 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Page 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...