IB IL 24 PSDO 8-PAC
PHOENIX CONTACT
7619_en_05
Cat. 3
–
Use proven safety principles.
–
Use appropriately qualified actuators (see Section “Requirements for controlled devic-
–
Please note that mechanical failure of the switching device can result in the loss of the
safety function.
–
Prevent the welding of contacts on the connected contactors or safety relays with ap-
propriate protection against overcurrent and surge voltage.
–
All errors (e.g., cross-circuits) that cannot be detected can result in the loss of the safety
function. Take appropriate measures to prevent such errors. Suitable measures in-
clude, for example, protected cable installation or double insulation. Please note the in-
formation in the following tables.
–
Please take into consideration errors with a common cause.
–
Ensure that
a single
error does not result in the loss of the safety function.
–
Once the test pulses have been disabled, test the shutdown capability of the actuators
at regular intervals.
Cat. 4
–
Use proven safety principles.
–
Use appropriately qualified actuators (see Section “Requirements for controlled devic-
–
Please note that mechanical failure of the switching device can result in the loss of the
safety function.
–
Prevent the welding of contacts on the connected contactors or safety relays with ap-
propriate protection against overcurrent and surge voltage.
–
An accumulation of errors must not result in the loss of the safety function. Following the
third error, evaluation can be aborted if the probability of further errors occurring is low.
–
All errors (e.g., cross-circuits) that cannot be detected can result in the loss of the safety
function. Take appropriate measures to prevent such errors. Suitable measures in-
clude, for example, protected cable installation or double insulation. Please note the in-
formation in the following tables.
–
Please take into consideration errors with a common cause.
–
Once the test pulses have been disabled, test the shutdown capability of the actuators
at regular intervals.
Summary of Contents for IB IL 24 PSDO 8-PAC
Page 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Page 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Page 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Page 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Page 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Page 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Page 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Page 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Page 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Page 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...