Technical data and ordering data
7619_en_05
PHOENIX CONTACT
Resistance of the housing material to fungal decay
Resistant
Ambient compatibility
Not resistant to chloroform
Connection data for Inline connectors
Connection method
Spring-cage terminal blocks
Conductor cross section
0.2 mm
2
to 1.5 mm
2
(solid or stranded), 24 - 16 AWG
Supported stop category according to EN 60204
0
1 im fehlerfreien Zustand
General data (Fortsetzung)
Mechanical requirements
Vibration according to IEC 60068-2-6
Operation: 2 g, Criterion A
Shock according to IEC 60068-2-27
15 g over 11 ms, Criterion A
Safety characteristic data according to IEC 61508/EN 61508
Achievable SIL
SIL 2 (single-channel)
SIL 3 (two-channel)
Depends on the parameterization and wiring (see Section
“Connection options for actuators depending on the param-
eterization” on page 22, Section “Connection examples for
Probability of a dangerous failure on demand by the safety
function (PFD)
SIL 2: 1% of 10
-2
, maximum (corresponds to 1 x 10
-4
)
SIL 3: 1% of 10
-3
, maximum (corresponds to 1 x 10
-5
)
Probability of a dangerous failure per hour for the entire mod-
ule (PFH)
SIL 2: 1 % of 10
-6
maximum (corresponds to 1 * 10
-8
)
SIL 3: 1 % of 10
-7
maximum (corresponds to 1 * 10
-9
)
Depends on the parameterization (see Table 6-3 on
Hardware fault tolerance (HFT) of the module
1
Permissible duration of use
20 a
Safety characteristic data according to EN 62061
Achievable SIL Claim limit
SILCL = SIL 2 (single-channel)
SILCL = SIL 3 (two-channel)
Depends on the parameterization and wiring (see Section
“Connection options for actuators depending on the param-
eterization” on page 22, Section “Connection examples for
Safe failure fraction (SFF)
99 %
Probability of a dangerous failure per hour for the entire mod-
ule (PFH)
SIL 2: 1 % of 10
-6
maximum (corresponds to 1 * 10
-8
)
SIL 3: 1 % of 10
-7
maximum (corresponds to 1 * 10
-9
)
Depends on the parameterization (see Table 6-3 on
Hardware fault tolerance (HFT) of the module
1
Permissible duration of use
20 a
Summary of Contents for IB IL 24 PSDO 8-PAC
Page 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Page 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Page 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Page 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Page 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Page 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Page 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Page 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Page 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Page 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...