Errors: Messages and removal
7619_en_05
PHOENIX CONTACT
8.3
Parameterization errors
In order to determine what type of parameterization error has occurred, use the correspond-
ing control software to access the safe controller online and read the error.
For example, with the SafetyProg software and INTERBUS-Safety proceed as follows:
•
Using the SafetyProg software, access the safe controller online.
•
Click on the “SafePLC” button.
•
Click on “Errors” in the window that opens.
The errors can now be read.
•
In the message window, switch to the “SafePLC Errors” tab.
The device-specific error code is displayed in decimal notation.
Table 8-3
Parameterization errors
Error cause
Error Code
(Hex)
LED
Comment
Effect
Remedy
Acknow
ledgme
nt
Incorrect
parameteriza-
tion
See
FS LED
(flash-
ing)
Each output is pa-
rameterized individ-
ually
Module is in the safe
state
Check and correct
parameterization.
–
Table 8-4
Parameterization errors
Error code
Short description
Remedy
(hex)
(dec)
021x
x = 0 ... 3:
OUT0_Ch1 ... OUT3_Ch1;
x = 7 ... A:
OUT0_Ch2 ... OUT3_Ch2
528
: OUT0_Ch1
:
531
: OUT3_Ch1;
535
: OUT0_Ch2
:
538
: OUT3_Ch2
The parameterized shutdown time for
the output is outside the permissible
value range.
INTERBUS-Safety only.
Correct value and resend parameter
data to the module.
022x
x = 0 ... 3:
OUT0_Ch1&2 ... OUT-
3_Ch1&2
545
: OUT0_Ch1&2
:
547
: OUT3_Ch1&2
For outputs parameterized for two-
channel operation, the same shutdown
times were not assigned.
INTERBUS-Safety only.
Correct value and resend parameter
data to the module.
023x
x = 0 ... 3:
OUT0_Ch1&2 ... OUT-
3_Ch1&2
560
: OUT0_Ch1&2
:
563
: OUT3_Ch1&2
The parameterization of two related
outputs does not correspond to the
two-channel setting.
Correct value and resend parameter
data to the module.
028x
x = 0 ... 3:
OUT0_Ch1 ... OUT3_Ch1;
x = 7 ... A:
OUT0_Ch2 ... OUT3_Ch2
640
: OUT0_Ch1
:
643
: OUT3_Ch1;
647
: OUT0_Ch2
:
650
: OUT3_Ch2
The parameterized switch-off delay
time for the output is outside the per-
missible value range.
Correct value and resend parameter
data to the module.
029x
x = 0 ... 3:
OUT0_Ch1&2 ... OUT-
3_Ch1&2
656
: OUT0_Ch1&2
:
659
: OUT3_Ch1&2
For outputs parameterized for two-
channel operation, the same settings
were not assigned for the switch-off de-
lay.
Correct setting and resend parameter
data to the module.
Summary of Contents for IB IL 24 PSDO 8-PAC
Page 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Page 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Page 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Page 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Page 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Page 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Page 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Page 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Page 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Page 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...