Auto On / Off with Manual Override
with Eco ON Light Level < 100%
Figure 3 above shows how daylight dimming takes place during Auto on/Auto off mode and the effect of manual overrides.
In case of manual override with a switch, lights can be dimmed up or down between the Task Level and Minimum dimming level.
When no occupancy is detected anymore, the timers (Hold Time and Prolong Time) get started.
In case occupancy is re-detected during Hold time, the existing light behavior continues and the timers are reset.
In case occupancy is re-detected during Prolong Time (or after), automatic light behavior starts and the timers are reset (as shown).
Task Level = 100%
Manually dimming up
Hold time
Prolong time
Automatic
behavior re-starts
even if prolong
time has not
elapsed
Grace
time
Manually dimming down
Eco-On Level = 80 %
Background light level = 20 %
Min dimming level = 1 %
Figure 3