![Philips EasySense SNS210 MC Installer/User Manual Download Page 27](http://html.mh-extra.com/html/philips/easysense-sns210-mc/easysense-sns210-mc_installer-user-manual_282648027.webp)
27
Remove/Reset devices from a group – safe mode
Purpose:
When the smartphone used to commission system is not available, components cannot be removed via the standard method. Instead, components shall be
reset via the Safe Mode.
How to:
The luminaires must be powered ON for more than 15 seconds.
• Power OFF mains for more than 10 seconds but less than 15 seconds (disconnect device from mains).
• Power ON mains for more than 2 seconds but less than 10 seconds (reconnect device to mains).
• Repeat above process for 4 times.
• On the 5th cycle, leave the fixtures powered ON at the end. You should see a short dim-down/dim-up signal. Sensors are now in Safe Mode.
• Scan with “Device Maintenance” to discover the sensors that are now In Safe Mode and Reset them, see screenshots below:
Click on three lines in
the right-bottom
corner
Click on “Settings”
Click on “Device
Maintenance”
Click on “Reset”
App will start
looking for devices
If Reset was
successful, no devices
in Safe Mode are
found (If devices are
still visible: press
“Reset” again)
If you want to add a
light in a group, they are
visible now
Click on “Select all”